beautypg.com

Walk-in, Fold membrane – Nor-Lake Capsule Pak Refrigeration Systems User Manual

Page 16

background image

16

07/14 Rev. H 040086

4. Set the Refrigeration System over

the opening in the curb. Remove

the enclosure from the condens-

ing unit portion of the system and

drill two 9/16” holes through the

condensing unit base plate, mem-

brane roof material and the foamed

ceiling section. The holes should

be located on opposite sides of the

unit. Insert one 1/2” threaded nylon

rod into each hole. Apply silicone

sealant around each nylon rod and

hole and place one washer and nut

on the condensing unit end of each

threaded nylon rod. Place a sec-

ond washer and nut on the inside

of the walk-in and tighten securely.

Replace the enclosure and attach

the outdoor hood with the drive

screws provided. Refer to Figure 3.

The nylon rods, washers, and nuts

are provided.

Note: Seal gasket at top of curb with silicone.

5. Fold all four corners of the membrane roofing material over

the walk-in corners as shown in Figure 4.

6. Attach the trim and door hood by using the provided hex

head sheet metal screws. All pieces should be held down

3-1/8” from the ceiling top as shown in Figure 5. Ensure the

trim and membrane roof material cover the joint between

the ceiling and wall panels. Note: The trim may have to be

cut to fit.

7. Trim off all excess membrane roofing material

from under the terminatin bar with a utility

knife. Do not allow the knife to cut the metal

panel, as this will damage the coating and

cause rust.

NOTe: In outdoor installations, the condensate

should be plumbed to the nearest drain. Check

local building codes. Outside drain lines must also

be wrapped with a suitable heater wire if they are

ever subjected to below freezing temperatures.

Fold Membrane

Membrane

Roofing Material

Figure 4

Figure 5

o

utdooR

S

yStemS

Capsule Pak™

With Hood

Membrane

Roofing

Opening

Walk-In

Figure 3