LoggerLink Settings
The following settings for LoggerLink can be viewed and/or set
from your device's Settings screen. Tap on LoggerLink under
Apps to display and change the settings.
Auto-Lock Settings: Prevent Auto-Lock
The Prevent Auto-Lock setting will prevent your device
from going to sleep when connected to a datalogger.
PakBus Settings: Global Address
The PakBus address for this device. Each device in a
PakBus network must have a unique address. Valid PakBus
addresses are 1 through 4094. Typically, software such as
LoggerLink should use a value greater than 3999. This is
because, when a neighbor filter is set up, a PakBus
datalogger will answer a Hello message from any device
with an ID greater than 3999, but will ignore devices with
IDs less than 4000 that are not in their neighbor list.
Troubleshooting: Logging Enabled
Enabling logging will create a low level log file of all
communications with a datalogger. Note that enabling
logging will slow down LoggerLink. Logging should only
be enabled, if you are experiencing communication
your computer. If you cannot email the log file, iTunes is
required to copy log files to your computer to be viewed.
32