Section 5. Program Declarations

5-5

Subroutine Example

'CR5000
'Declare Variables used in Program:
Public RefT, TC(4),PRTresist,PRTtemp,I

'Data output in deg C:
DataTable (TempsC,1,-1)

DataInterval (0,5,Min,10)
Average (1,RefT,FP2,0)
Average (4,TC(),FP2,0)
Average (1,PRTtemp,FP2,0)

EndTable

'Same Data output in F:
DataTable (TempsF,1,-1)

DataInterval (0,5,Min,10)
Average (1,RefT,FP2,0)
Average (4,TC(),FP2,0)
Average (1,PRTtemp,FP2,0)

EndTable

'Subroutine to convert temperature in degrees C to degrees F
Sub ConvertCtoF (Tmp)

Tmp = Tmp*1.8 +32

EndSub

BeginProg

Scan (1,Sec,3,0)

'Measure Temperatures (panel, 4 thermocouples, and 100 ohm PRT) in deg C
PanelTemp (RefT,250)
TCDiff (TC(),4,mV20C ,1,TypeT,RefT,True ,0,250,1.0,0)
Resistance (PRTresist,1,mV50,7,Ix1,1,500,True ,True ,0,250,0.01,0)
PRT (PRTtemp,1,PRTresist,1.0,0)
'Call Output Table for C
CallTable TempsC
'Convert Temperatures to F using Subroutine:
Call ConvertCtoF(RefT)

'Subroutine call using Call statement

For I = 1 to 4

ConvertCtoF(TC(I))

'Subroutine call without Call statement

Next I
ConvertCtoF(PRTtemp)

'Subroutine call without Call statement

'Call Output Table for F:
CallTable TempsF

NextScan

EndProg