Appendix A. CR5000 Status Table
A-3
DLDBytesFree - Amount of free space in the CPU RAM disk that is used to
store program files.
ProcessTime - Time in microseconds that it took to run through processing on
the last scan. Time is measured from the end of the EndScan instruction (after
the measurement event is set) to the beginning of the EndScan (before the wait
for the measurement event begins) for the subsequent scan.
MaxProcTime - The maximum time required to run through processing for
the current scan. This value is reset when the scan exits.
MeasureTime - The time required by the hardware to make the measurements
in this scan. The sum of all integration times and settling times. Processing will
occur concurrent with this time so the sum of measure time and process time is
not the time required in the scan instruction.
SkippedScan - Number of scans that have occurred while running the current
program.
SlowProcTime - Time required to process the current slow scan. If the user
has slow scans then this variable becomes an array with a value for the system
slow scan and each of the users scans.
MaxSlowProcTime - The maximum Time required to process the current slow
scan. If the user has slow scans then this variable becomes an array with a
value for the system slow scan and each of the users scans.
LastSlowScan - The last time that this slow scan executed. If the user has slow
scans then this variable becomes an array with a value for the system slow scan
and each of the users scans.
SkippedSlowScan - The number of scans that have been skipped in this slow
sequence. If the user has slow scans then this variable becomes an array with a
value for the system slow scan and each of the users scans.
MeasureOps - This is the number of task sequencer opcodes required to do all
measurements in the system. This value includes the Calibration opcodes
(compile time) and the system slow sequence opcodes.
WatchdogErrors - The number of Watchdog errors that have occurred while
running this program. This value can be reset from the keyboard by going to
status and scrolling down to the variable and pressing the DEL key. It is also
reset upon compiling a new program.
Low12VCount - Keeps a running count of the number of occurrences of the
12VLow signal being asserted. When this condition is detected the logger
ceases making measurements and goes into a low power mode until the system
voltage is up to a safe level. This value can be reset from the keyboard by
going to status and scrolling down to the variable and pressing the DEL key. It
is also reset upon compiling a new program.
StartUpCode - A code variable that allows the user to know how the system
woke up from poweroff.