Section 7. Measurement Instructions

7-24

CR23X

Pi

20k

FIGURE 7.8-1. Conditioning Large Voltage Pulses

The maximum input voltage on a pulse channel is

±20 V. Refer to Figure

7.8-1 if reducing input voltage is required.

• Pulse Channels

Maximum Input Voltage:

±20 V

High Frequency Input

• Pulse Channels

Minimum Pulse Width: 1.2 microsecond
Maximum Frequency: 400 kHz

(50% Duty Cycle)

Lower Threshold: 1.5 V*
Upper Threshold: 3.5 V*

When a pulse channel is configured for high-frequency pulse, there is an
internal 100 kohm pull-up resistor to 5 V on the pulse channel. This pull-up
resistor accommodates open-collector output devices for high-frequency input.

*Larger input transitions are required at high frequencies because of the input
RC filter with 1.2 microsecond time constant. Signals up to 400 kHz will be
counted if centered around +2.5 V with deviations

≥ ± 2.5 V for ≥ 1.2

microseconds.

Low Level AC (Pulse Channels Only)

Input Hysteresis: 15 mV
Maximum Input Voltage: 20 V peak-to-peak
Input Voltage and Frequency Range

(16 bit counter required above 2.56 kHz)
20 mV

1.0 Hz to 1 kHz

200 mV

0.5 Hz to 10 kHz

1000 mV

0.3 Hz to 16 kHz

CR5000