7 self measurements, Battery (dest), Paneltemp (dest, integ) – Campbell Scientific CR5000 Measurement and Control Module User Manual
Page 141

Section 7. Measurement Instructions
7-15
Parameter 
& Data Type 
Enter
ExChan
Enter the excitation channel number to excite the first measurement.
Constan
Alpha 
Code 
Code/ 
Channel 
Result
VX1 1
Switched excitation channels, are switched to the excitation 
voltage. 
VX2 2
for the measurement and switched off between measurements.
VX3 3
VX4 4
ExmV 
Constant 
The excitation voltage in millivolts. Allowable range ± 5000 mV.
XDelay 
 
Specifies the length of time the excitation is enabled, after which, the channel is 
set low and the datalogger moves on to the next instruction. If XDelay is set to 0, 
the excitation will be on until the end of the program scan or until another 
instruction sets an excitation voltage, CAO, or current channel.
7.7 Self Measurements
Battery (Dest)
This instruction reads the battery voltage and stores it in the destination 
variable. The units for battery voltage are volts. 
PanelTemp (Dest, Integ)
This instruction measures the panel temperature in
°C.
Parameter 
& Data Type 
Enter
Dest
Variable or 
Array
The Variable in which to store the results of the instruction. When Reps are used the 
results are stored in an array with the variable name. An array must be dimensioned to 
have elements for all the Reps. 
Integ
The time spent on integration in microseconds for each of the channels measured.
Constant
Entry
Integration
0, 200
Flash Conversion; 200 = 2 flash conversions 100 µS apart 
and averaged 
250; 500-16000
250 µS; multiples of 500: 250 µS integrations starting each 
500 µS 
_60Hz or 16667
16,667 µS (reject 60 Hz noise)
_50 Hz or 20000
20,000 µS (reject 50 Hz noise)