7.1.2 Limit value curve
Evaluation of steam trap surface temperatures:

Fig. 6

Leaking !

Te

mperature in °C / st

ructure-borne sound level

p in bar(ü)

A measurement with headphones is recommended

at low steam pressures in order to obtain a clear

result.

Borderline

Steam trap OK acc. to

temperature measurement

Cold or blocked

Steam trap OK acc. to

ultrasonic measurement

Temp. measurement

Limit value curve

for ultrasound

Lower limit temperature

Surface t

min external

°C

Surface t

external

°C

Upper limit temperature for

thermostatic steam traps
Surface t

max external

°C

Limit value for ultrasound