beautypg.com

Emc installation guidelines – Red Lion TLA User Manual

Page 3

background image

3

OUTPUT SPECIFICATIONS

1. LIMIT AND ALARM OUTPUT RELAYS:

Contact Rating: 5 A @ 250 VAC or 30 VDC (resistive load).

Life Expectancy: 100,000 cycles at max. load rating. (Decreasing load

increases life expectancy.)

2. LIMIT OUTPUT: TLA21000: Form-C relay; TLA11100: Form-A relay.

Selectable for high or low trip activation. If the process temperature goes

above the limit setpoint for a high trip, or below the limit setpoint for a low

trip, the limit relay will de-energize to initiate a process shutdown. The limit

output cannot be reset until the process temperature returns to the proper

operating range; manual reset is required (local or remote).

Annunciators:

“EX” - Lit when the process temperature exceeds the limit setpoint.

“OUT” - Lit when the limit output is de-energized.

3. ALARM OUTPUTS (Optional): One or two Form-A relays.

Modes:

Absolute High Acting

Absolute Low Acting

Deviation High Acting

Deviation Low Acting

Inside Band Acting

Outside Band Acting

Reset Action: Programmable; automatic or latched. Latched alarms can be

reset regardless of limit exceed condition.

Standby Mode: Programmable; enable or disable.

Hysteresis: Programmable.

Annunciator: “A1” and “A2” programmable for normal or reverse acting.

Although Red Lion Controls Products are designed with a high degree of

immunity to Electromagnetic Interference (EMI), proper installation and wiring

methods must be followed to ensure compatibility in each application. The type

of the electrical noise, source or coupling method into a unit may be different

for various installations. Cable length, routing, and shield termination are very

important and can mean the difference between a successful or troublesome

installation. Listed are some EMI guidelines for a successful installation in an

industrial environment.
1. A unit should be mounted in a metal enclosure, which is properly connected

to protective earth.

2. Use shielded cables for all Signal and Control inputs. The shield connection

should be made as short as possible. The connection point for the shield

depends somewhat upon the application. Listed below are the recommended

methods of connecting the shield, in order of their effectiveness.

a. Connect the shield to earth ground (protective earth) at one end where the

unit is mounted.

b. Connect the shield to earth ground at both ends of the cable, usually when

the noise source frequency is over 1 MHz.

3. Never run Signal or Control cables in the same conduit or raceway with AC

power lines, conductors, feeding motors, solenoids, SCR controls, and

heaters, etc. The cables should be run through metal conduit that is properly

grounded. This is especially useful in applications where cable runs are long

and portable two-way radios are used in close proximity or if the installation

is near a commercial radio transmitter. Also, Signal or Control cables within

an enclosure should be routed as far away as possible from contactors,

control relays, transformers, and other noisy components.

4. Long cable runs are more susceptible to EMI pickup than short cable runs.
5. In extremely high EMI environments, the use of external EMI suppression

devices such as Ferrite Suppression Cores for signal and control cables is

effective. The following EMI suppression devices (or equivalent) are

recommended:

Fair-Rite part number 0443167251 (RLC part number FCOR0000)

Line Filters for input power cables:

Schaffner # FN2010-1/07 (Red Lion Controls # LFIL0000)

6. To protect relay contacts that control inductive loads and to minimize radiated

and conducted noise (EMI), some type of contact protection network is

normally installed across the load, the contacts or both. The most effective

location is across the load.

a. Using a snubber, which is a resistor-capacitor (RC) network or metal oxide

varistor (MOV) across an AC inductive load is very effective at reducing

EMI and increasing relay contact life.

b. If a DC inductive load (such as a DC relay coil) is controlled by a transistor

switch, care must be taken not to exceed the breakdown voltage of the

transistor when the load is switched. One of the most effective ways is to

place a diode across the inductive load. Most RLC products with solid

state outputs have internal zener diode protection. However external diode

protection at the load is always a good design practice to limit EMI.

Although the use of a snubber or varistor could be used.

RLC part numbers: Snubber: SNUB0000

Varistor: ILS11500 or ILS23000

7. Care should be taken when connecting input and output devices to the

instrument. When a separate input and output common is provided, they

should not be mixed. Therefore a sensor common should NOT be connected

to an output common. This would cause EMI on the sensitive input common,

which could affect the instrument’s operation.
Visit RLC’s web site at http://www.redlion.net/Support/InstallationConsiderations.

html for more information on EMI guidelines, Safety and CE issues as they

relate to Red Lion Controls products.

EMC INSTALLATION GUIDELINES

RBD48111

RBDLA210

REPLACEMENT

OUTPUT BOARD

TLA11100

Form-A Relay

Form-A Relay

Form-A Relay

TLA21000

Form-A Relay

Form-C Relay

PART NUMBERS

ALARM 2 OUTPUT

ALARM 1 OUTPUT

LIMIT OUTPUT

18 to 36 VDC / 24 VAC

85 to 250 VAC

RBD48111

RBDLA210

REPLACEMENT

OUTPUT BOARD

TLA11110

Form-A Relay

Form-A Relay

Form-A Relay

TLA21010

Form-A Relay

Form-C Relay

PART NUMBERS

ALARM 2 OUTPUT

ALARM 1 OUTPUT

LIMIT OUTPUT

ORDERING INFORMATION