beautypg.com

Wiring connections, Cub4lp/cl signal input, Offset adjustments – Red Lion CUB4LP User Manual

Page 3: Span adjustments, Emc installation guidelines, Backlight power (cub4cl only)

background image

3

WIRING CONNECTIONS

All conductors should meet voltage and current ratings for

each terminal. Also cabling should conform to appropriate

standards of good installation, local codes and regulations. It is

recommended that power supplied to the unit (AC or DC) be

protected by a fuse or circuit breaker.

The electrical connections are made via screw-clamp terminals

located on the back of the unit. When wiring the unit, use the

label to identify the wire position with the proper function. Strip

the wire, leaving approximately ¼" of bare wire (stranded wires

should be tinned with solder). Insert the wire into the screw-

clamp terminal and tighten the screw until the wire is clamped

tightly. Each terminal can accept up to two #14 AWG wires.

4

2

1

3

VDC +

SIG +

COM

SIG -

(SENSOR)

(CL ONLY)

(CL ONLY)

(SENSOR)

(CL)

(CL)

V+

SIG.+

1 COM

SIG.-

4

2

4

3

2

1

ON

0.000

0.00

0.0

10-5

0

FIN

E

CUB4LP/CL

3

COA

RSE

COA

RSE

FIN

E

SPAN

OFFSET

1 2 3 4

SPAN

OFFSET

COA

RSE

FIN

E

COA

RSE

FIN

E

0.0

0.00

0.000

10-5

0

RED LION CONTROLS

YORK, PA. MADE IN U.S.A.

M1721C

CUB4LP/CL SIGNAL INPUT

The current range is selected by setting DIP switch S1 to the OFF position

for a 4 to 20 mA input or ON for a 10 to 50 mA input. Attach the signal wires

to terminals 3 (SIG-) and 4 (SIG+) observing the correct polarity. The (SIG-)

signal input circuit is not reverse polarity protected.

Backlight Power (CUB4CL only)

Attach a 9 to 28 VDC supply to terminals 1 (COM) and 2 (V+) to power the

backlight. Terminals 3 (SIG-) and 1 (COM) are AC coupled with a capacitor.

This limits the isolation between these terminals to 50 VDC maximum.

OFFSET ADJUSTMENTS

The minimum currents are not zero based with 4 to 20 mA and 10 to 50 mA

signals. To obtain a zero minimum display reading, the display must be offset.

The display on the CUB4LP/CL can be offset by adjusting the Coarse and Fine

Offset pots.

SPAN ADJUSTMENTS

Span is defined as the numerical range that the display traverses, disregarding

the decimal point, when the input signal is varied from minimum to maximum

(4 to 20 mA or 10 to 50 mA). For example; if a unit is to display 250 @ 4 mA

and 1000 @ 20 mA, the span is 750 (the difference between 250 and 1000). Had

the minimum display been -250, the span would be 1250 (1000 - (-250) = 1250).

The CUB4LP/CL can be set to operate over a wide span range by adjusting the

Coarse and Fine Span adjustment pots. The Coarse Span pot is used to get the

display to within a couple of counts of the desired reading, and the Fine Span

pot is used to adjust for the exact reading.

WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT

EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF

OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.

THIS EQUIPMENT IS SUITABLE FOR USE IN:

Class I, Division 2, Groups A, B, C, and D

Class II, Division 2, Groups F and G

Class III, Division 2 or Non Hazardous locations.

EMC INSTALLATION GUIDELINES

Although Red Lion Controls Products are designed with a high degree of

immunity to Electromagnetic Interference (EMI), proper installation and wiring

methods must be followed to ensure compatibility in each application. The type

of the electrical noise, source or coupling method into a unit may be different

for various installations. Cable length, routing, and shield termination are very

important and can mean the difference between a successful or troublesome

installation. Listed are some EMI guidelines for a successful installation in an

industrial environment.

1. A unit should be mounted in a metal enclosure, which is properly connected

to protective earth.

2. Use shielded cables for all Signal and Control inputs. The shield connection

should be made as short as possible. The connection point for the shield

depends somewhat upon the application. Listed below are the recommended

methods of connecting the shield, in order of their effectiveness.

a. Connect the shield to earth ground (protective earth) at one end where the

unit is mounted.

b. Connect the shield to earth ground at both ends of the cable, usually when

the noise source frequency is over 1 MHz.

3. Never run Signal or Control cables in the same conduit or raceway with AC

power lines, conductors, feeding motors, solenoids, SCR controls, and

heaters, etc. The cables should be run through metal conduit that is properly

grounded. This is especially useful in applications where cable runs are long

and portable two-way radios are used in close proximity or if the installation

is near a commercial radio transmitter. Also, Signal or Control cables within

an enclosure should be routed as far away as possible from contactors, control

relays, transformers, and other noisy components.

4. Long cable runs are more susceptible to EMI pickup than short cable runs.

5. In extremely high EMI environments, the use of external EMI suppression

devices such as Ferrite Suppression Cores for signal and control cables is

effective. The following EMI suppression devices (or equivalent) are

recommended:

Fair-Rite part number 0443167251 (RLC part number FCOR0000)

Line Filters for input power cables:

Schaffner # FN2010-1/07 (Red Lion Controls # LFIL0000)

6. To protect relay contacts that control inductive loads and to minimize radiated

and conducted noise (EMI), some type of contact protection network is

normally installed across the load, the contacts or both. The most effective

location is across the load.

a. Using a snubber, which is a resistor-capacitor (RC) network or metal oxide

varistor (MOV) across an AC inductive load is very effective at reducing

EMI and increasing relay contact life.

b. If a DC inductive load (such as a DC relay coil) is controlled by a transistor

switch, care must be taken not to exceed the breakdown voltage of the

transistor when the load is switched. One of the most effective ways is to

place a diode across the inductive load. Most RLC products with solid state

outputs have internal zener diode protection. However external diode

protection at the load is always a good design practice to limit EMI.

Although the use of a snubber or varistor could be used.

RLC part numbers: Snubber: SNUB0000

Varistor: ILS11500 or ILS23000

7. Care should be taken when connecting input and output devices to the

instrument. When a separate input and output common is provided, they

should not be mixed. Therefore a sensor common should NOT be connected

to an output common. This would cause EMI on the sensitive input common,

which could affect the instrument’s operation.
Visit RLC’s web site at http://www.redlion.net/Support/InstallationConsiderations.

html for more information on EMI guidelines, Safety and CE issues as they

relate to Red Lion Controls products.

This manual is related to the following products: