beautypg.com

Pecifications, Dimensions in inches (mm) – Red Lion G315 15" TFT Color Touch Panel User Manual

Page 2

background image

2

1. POWER REQUIREMENTS:

Must use Class 2 or SELV rated power supply.
Power connection via removable three position terminal block.

Supply Voltage:

+24 VDC ±20%

Typical Power

1

: 27

W

Maximum Power

2

: 67

W

Notes:

1. Typical power with +24 VDC, RS232/485 communications, Ethernet

communications, CompactFlash card installed, and display at full brightness.

2. Maximum power indicates the most power that can be drawn from the

G315C. Refer to “Power Supply Requirements” under “Installing and
Powering the G315C.”

3. The G315C’s circuit common is not connected to the enclosure of the

unit. See “Connecting to Earth Ground” in the section “Installing and
Powering the G315C.”

4. Read “Power Supply Requirements” in the section “Installing and

Powering the G315C” for additional power supply information.

2. BATTERY: Lithium coin cell. Typical lifetime of 10 years.
3. LCD DISPLAY:

*Lifetime at room temperature. Refer to “Display” in “Software/Unit Operation”
4. 10-KEY KEYPAD: for on-screen menus.
5. TOUCHSCREEN: Resistive analog
6. MEMORY:

On Board User Memory: 32 Mbyte of non-volatile Flash memory.
Memory Card: CompactFlash Type II slot for Type I and Type II

CompactFlash cards.

7. COMMUNICATIONS:

USB Device Port: Adheres to USB 2.0 Specification supporting high speed

and full speed via Type B connection.

Serial Ports: Format and Baud Rates for each port are individually software

programmable up to 115,200 baud.
PGM Port: RS232 port via RJ12.
COMMS Ports: RS422/485 port via RJ45, and RS232 port via RJ12.
DH485 TXEN: Transmit enable; open collector, V

OH

= 15 VDC,

V

OL

= 0.5 V @ 25 mA max.

Note: For additional information on the communications or signal

common and connections to earth ground please see the “Connecting to
Earth Ground” in the section “Installing and Powering the G315C.”

Port to port isolation: 500 Vrms for 1 minutes signal isolation : 50V

Ethernet Port: 10 BASE-T / 100 BASE-TX

RJ45 jack is wired as a NIC (Network Interface Card).
Isolation from Ethernet network to G3 operator interface: 1500 Vrms

8. ENVIRONMENTAL CONDITIONS:

Operating Temperature Range: 0 to 50 °C
Storage Temperature Range: -20 to 70 °C

Operating and Storage Humidity: 80% maximum relative humidity (non-

condensing) from 0 to 50°C.

Vibration according to IEC 68-2-6: Operational 5 to 150 Hz, in X, Y, Z

direction for 1.5 hours, 2 g’s.

Shock according to IEC 68-2-27: Operational 35 g’s, 9 msec in 3 directions.
Altitude: Up to 2000 meters.

9. CERTIFICATIONS AND COMPLIANCES:

SAFETY
UL Recognized Component, File #E179259, UL61010-1, CSA 22.2 No.61010-1

Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.

UL Listed, File #E211967, UL61010-1, ANSI/ISA 12.12.01-2007, CSA 22.2

No. 61010.1, CSA 22.2 No. 213-M1987
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards

Type 4X Enclosure rating (Face only), UL50
IECEE CB Scheme Test Certificate #US/12460C/UL,

CB Scheme Test Report #E179259-A1-CB-1

Issued by Underwriters Laboratories Inc.

IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment

for measurement, control, and laboratory use, Part 1.

IP66 Enclosure rating (Face only), IEC 529

ELECTROMAGNETIC COMPATIBILITY
Emissions and Immunity to EN 61326: Electrical Equipment for Measurement,

Control and Laboratory use.

Note:

1. Criterion A: Normal operation within specified limits.
2. Criterion B: Temporary loss of performance from which the unit self
recovers.

10. CONNECTIONS: Compression cage-clamp terminal block.

Wire Gage: 12-22 AWG copper wire
Torque: 5-7 inch-pounds (56-79 N-cm)

11. CONSTRUCTION: Steel rear metal enclosure with NEMA 4X/IP66

aluminum front plate for indoor use only when correctly fitted with the gasket
provided. Installation Category II, Pollution Degree 2.

12. MOUNTING REQUIREMENTS: Maximum panel thickness is 0.25" (6.3

mm). For NEMA 4X/IP66 sealing, a steel panel with a minimum thickness of
0.125" (3.17 mm) is recommended.
Maximum Mounting Stud Torque: 17 inch-pounds (1.92 N-m)

13. WEIGHT: 11.41 lbs (5.17 Kg)

16.00 (406.4)

13.00

(330.2)

14.59 (370.6)

11.59

(294.4)

.28

(7.1)

PROTECTIVE EARTH GROUND

2.8

(71.5)

DIMENSIONS In inches (mm)

S

PECIFICATIONS

15-inch

TFT

32K

1024 X 768

600 cd/m

2

50,000 HR TYP.

Class A

EN 55011

Emissions

Emissions:

3 V/rms

Criterion B

EN 61000-4-6

RF conducted interference

2 kV L&N-E power

2 kV power

Criterion B

EN 61000-4-4

Fast transients (burst)

Criterion A

EN 61000-4-5

Surge

1 kV L-L,

10 V/m

Criterion B

EN 61000-4-3

Electromagnetic RF fields

1 kV signal

8 kV air discharge

4 kV contact discharge

Criterion A

EN 61000-4-2

Electrostatic discharge

Immunity to Industrial Locations:

WARNING - DO NOT CONNECT OR DISCONNECT CABLES WHILE

POWER IS APPLIED UNLESS AREA IS KNOWN TO BE NON-

HAZARDOUS. USB PORT IS FOR SYSTEM SET-UP AND
DIAGNOSTICS AND IS NOT INTENDED FOR PERMANENT

CONNECTION.

SIZE

TYPE

COLORS

PIXELS

BRIGHTNESS

BACKLIGHT*