AC WIRING NOTES

AC HOT OUT

AC NEUTRAL OUT

CHASSIS GROUND/PE

CHASSIS GROUND/PE

AC NEUTRAL IN

AC HOT IN

BATTERY

FULL

OK

LOW

STATUS

INVERTER

AC IN

ERROR

BATTERY TEMP

MATE/HUB

INVERTER ON/OFF

INVERTER

ON/OFF

AUX+

AUX-

XCT-

XCT+

AC HOT (PHASE) OUT

• Supplies the AC hot output conductors

through a 30 amp maximum AC branch
rated circuit breaker using 6 AWG (16.0 mm

2

)

wire and connect to the AC

AC NEUTRAL OUT/AC NEUTRAL IN

• Connects the AC neutral input conductor to

the AC NEUTRAL IN terminal.

• Connects the AC neutral output conductor

to the AC NEUTRAL OUT terminal.

AC HOT (PHASE) IN

• The AC hot input conductor (brown) must

be supplied through a 30 amp maximum AC
branch rated circuit breaker and connected
to the AC HOT IN.

• 6 AWG (16.0 mm

2

) wire is required for the

FX’s AC transfer relay.