Installing in complete system shelter – DAVIS Radio Surge Protector User Manual
Page 2

Page 2
Radio Surge Protector
I
NSTALLING
IN
C
OMPLETE
S
YSTEM
S
HELTER
Follow the instructions below to install the Radio Surge Protector (referred to
as the protector) in the Complete System Shelter (CSS).
1. Using a 7/32" drill bit, drill a hole in the CSS in the location shown below.
2. Install the protector and ground lug as shown below, using the #10-32 x 1" (25 mm)
machine screw and the tooth lock washers and #10 hex nut from the mounting hard-
ware kit supplied with the protector.
Note:
Do not use the spacer when installing in the CSS.
3. Insert one end of the ground wire into the ground lug and tighten.
The use of a heavier ground wire or strap is recommended if nearby light-
ning strikes are likely.
4. Attach the other end of the ground wire to a suitable earth ground.
5. Connect the cable coming from the antenna to the ANTENNA side of the protector and
the cable from the modem to the EQUIPMENT side of the protector.
Consult the manual supplied with your installation kit for exact cabling
instructions.
User-Drilled Hole
7/32" Diameter
(.218", 5.5 mm)
Machine
Screw
Lock
Washer
Lock
Washer
Hex Nut
Radio
Surge
Protector
6.0" (152 mm)
2.0" (51 mm)
Ground Lug
Ground
Wire
Note: Aluminum Spacer not used.
Centerline
of Shelter