Installation

Mounting

24

Unimode 9600 PN 51336:C 11/06/01

SECTION 2

Installation

The cabinet may be either semi-flush or surface mounted. The cabinet mounts using two
key slots and two 0.250” (6.35 mm) diameter holes located in the backbox. The key slots
are located at the top of the backbox and the two securing holes at the bottom.

Carefully unpack the system and check for shipping damage. Mount the cabinet in a
clean, dry, vibration-free area where extreme temperatures are not encountered. The area
should be readily accessible with sufficient room to easily install and maintain the panel.
Locate the top of the cabinet approximately 5 feet (1.5 m) above the floor with the hinge
mounting on the left. Determine the number of conductors required for the devices to be
installed. Sufficient knockouts are provided for wiring convenience. Select the
appropriate knockout(s) and pull the conductors into the box. All wiring should be in
accordance with the National and/or Local codes for fire alarm systems.

2.1 Mounting

The circuit board contains static-sensitive components. Always ground yourself with a
proper wrist strap before handling any boards so that static charges are removed from the
body. Use static suppressive packaging to protect electronic assemblies.

✓ Mark and predrill holes in the wall for the top two keyhole mounting bolts using

the dimensions illustrated in Figure 2.2 on page 25

✓ Install two upper fasteners in the wall with the screw heads protruding
✓ Using upper ‘keyholes,’ place backbox over the two screws, level and secure
✓ Mark and drill the lower two holes
✓ Mount backbox, install remaining fasteners and tighten
✓ Screw supplied standoffs onto mounting studs in locations indicated below
✓ When the location is dry and free of construction dust, install the main circuit

board by aligning the 10 mounting holes in the circuit board with the 10

mounting standoffs in the backbox as illustrated below

✓ Secure the circuit board to the standoffs with the supplied screws and male/

female standoff as indicated in following figure

!

See Page

+BATTERY-

LCD DISPLAY

KEYPAD I/F

OPT DACT

HOT

CB1

J3

J2

TB1

TB2

TB3

JP3

JP2

SW1

JP5

JP6

J17

J16

J6

J8

J7

JP10

JP11

CUT TO

DISABLE
LOCAL
CHARGER

DISABLE

GND
FLT

CUT TO
MONITOR 4XTM

OPT SLC

4XTM OPT BD

TB4

TB5

TB6

TB7

TB8

NEUT EARTH

Figure 2.1 Unimode 9600 Main Circuit Board Installation

Unimode 9600 Backbox

Unimode 9600 Main Circuit Board

mounting studs

mounting studs

96brdmnt

.c

dr

IMPORTANT!
Secure circuit board to this standoff
with supplied male/female standoff