3URFHVV 0RQLWRU 2SHUDWLRQ

2SHUDWLQJ ,QVWUXFWLRQV

8QLPRGH 31 &

4.7 Process Monitor Operation

Process Monitor operation will initiate the following events:

• The piezo sounder pulses ¼ second On and ¼ second Off
• The LCD displays a process monitor message along with the device name, type,

address, adjective/noun, associated zones and time/date

• Relays programmed for process monitoring will be activated
• The alarm relay is not activated
• Silenced alarms are not resounded
• Timers are not started
• Store event in history buffer

Note that, like supervisories, process monitor signals latch (except when programmed for
process monitor autoresettable) and can be assigned to software zones.

4.8 Hazard Condition Operation

Hazard Condition operation will initiate the following events:

• The piezo sounder turns on steady
• The LCD displays a hazard message along with the device name, type, address,

adjective/noun, associated zones and time/date

• Relays programmed for process monitoring will be activated
• The alarm relay is not activated
• Silenced alarms are not resounded
• Timers are not started
• Store event in history buffer

Hazard conditions do not latch and will therefore clear when the hazard condition is
cleared. They can be assigned to software zones.

4.9 Medical Alert Condition Operation

Medical Alert Condition operation will initiate the following events:

• The piezo sounder turns on steady
• The LCD displays a medical alert message along with the device name, type,

address, adjective/noun, associated zones and time/date

• Relays programmed for medical alert will be activated
• The alarm relay is not activated
• Silenced alarms are not resounded
• Timers are not started
• Store event in history buffer

Medical alert conditions do not latch and will therefore clear when the medical alert
condition is cleared. They can be assigned to software zones.

4.10 NAC Operation

There are two programmable NACs (Notification Appliance Circuits) resident on the
Unimode 9600 main circuit board. Both NACs may be programmed as silenceable or
nonsilenceable and may also be programmed for steady or coded operation. Coded
operation provides a choice between March Time, Temporal or California coding.