Environmental requirements and specifications

Environmental requirements

NOTE:

For operating and non-operating environmental technical specifications, see QuickSpecs:

http://www.hp.com/support/msa2040/QuickSpecs

.

Electrical requirements

Site wiring and power requirements

Each enclosure has two power supply modules for redundancy. If full redundancy is required, use a

separate power source for each module. The AC power supply unit in each power supply module is

auto-ranging and is automatically configured to an input voltage range from 88–264 VAC with an input

frequency of 47–63 Hz. The power supply modules meet standard voltage requirements for both U.S. and

international operation. The power supply modules use standard industrial wiring with line-to-neutral or

line-to-line power connections.

Power cord requirements

Each enclosure is equipped with two power supplies of the same type (both AC or both DC). For

enclosures equipped with AC power supply modules, use two power cords that are appropriate for use in

a typical outlet in the destination country. Whether using AC or DC power supplies, each power cable

connects one of the power supplies to an independent, external power source. To ensure power

redundancy, connect the two suitable power cords to two separate circuits; for example, to one commercial

circuit and one uninterruptible power source (UPS).

IMPORTANT:

See QuickSpecs for information about power cables provided with your MSA 2040

Storage product.