beautypg.com

Hp 750 w cs -48 v dc power supply (94% efficiency) – HP ProLiant DL320e Gen8 v2-Server User Manual

Page 82

background image

Specifications 82

Power supply output

Efficiency

80%

Maximum peak power

250 W

HP 750 W CS -48 V DC Power Supply (94% efficiency)

Specification

Value

Input requirements

Rated input voltage

-36 V DC to -72 V DC
-48 V DC nominal input

Rated input current

23 A at -36 V DC input

17 A at -48 V DC input, nominal
input

11 A at -72 V DC input

Rated input power (W)

815 W at -36 V DC input

805 W at -48 V DC input, nominal
input

795 W at -72 V DC input

Rated input power (Btus per
hour)

2780 at -36 V DC input

2740 at -48 V DC input, nominal
input

2720 at -72 V DC input

Power supply output

Rated steady-state power (W) 750 W
Maximum peak power (W)

750 W

CAUTION:

This equipment is designed to permit the connection of the earthed conductor of the

DC supply circuit to the earthing conductor at the equipment.

If this connection is made, all of the following must be met:

This equipment must be connected directly to the DC supply system earthing electrode

conductor or to a bonding jumper from an earthing terminal bar or bus to which the DC supply

system earthing electrode conductor is connected.

This equipment must be located in the same immediate area (such as adjacent cabinets) as any
other equipment that has a connection between the earthed conductor of the same DC supply

circuit and the earthing conductor, and also the point of earthing of the DC system. The DC

system must be earthed elsewhere.

The DC supply source is to be located within the same premises as the equipment.

Switching or disconnecting devices must not be in the earthed circuit conductor between the

DC source and the point of connection of the earthing electrode conductor.