beautypg.com

Thermal and air flow performance, Environmental specifications, Hp 11642 1200mm rack specifications – HP Modular Cooling System User Manual

Page 56

background image

Specifications 56

Thermal and air flow performance

Maximum thermal and air flow

performance parameters

Single rack

Dual rack
(Specification per rack)

Air temperature—Inlet to rack-mounted
components

25ºC (68ºF)

25ºC (68ºF)

Chilled water temperature

7º–18°C (45º–64°F)

7º–18°C (45º–64°F)

Total rack-mounted component air flow 3,000 cfm (5,100 m3/h) or less at

0 or more pressure drop across the
rack mounted components

1,500 cfm (2,250 m3/h) or less at
0 or more pressure drop across the
rack mounted components

Chilled water flow rate

50 l/min (13.2 US gal/min)

50 l/min (13.2 US gal/min)

Chilled water pressure differential at

flow needed to meet thermal
specifications

1.0 bar delta pressure

1.0 bar delta pressure

Heat lost to room

Approximately 10% maximum

depending on the MCS settings
and room temperature

Approximately 10% maximum

depending on the MCS settings
and room temperature

Server heat load

30 kW maximum

15 kW maximum

Environmental specifications

Features

Specifications

Operating temperature:
Recommended

Allowable


18ºC (64.4ºF) to 27ºC (80.6ºF)
15ºC to 32ºC (59ºF to 90ºF)

Non-operating temperature 0ºC to 60ºC (32ºF to 140ºF)
Transit temperature

-30ºC to 60ºC (-22ºF to 140ºF), up to 72 hours

Storage temperature

-20ºC to 60ºC (-4ºF to 140ºF)

Operating humidity:

Recommended minimum
Recommended maximum
Allowable range


5.5°C (41.9°F) dew point

60% relative humidity and 15°C (59°F) dew point
20 to 80% relative humidity (non-condensing)

Non-operating humidity

5 to 95% relative humidity (non-condensing)

Operating altitude

-76.2 to 3,048 m (-250 to 10,000 ft)

Non-operating altitude

-76.2 to 9,144 m (-250 to 30,000 ft)

NOTE:

For safety, the MCS-100 unit is equipped with a dew point sensor and control system

which creates an alarm that sounds if the chilled water temperature is lower than the dew point
temperature. This condition might create excessive condensation on the heat exchanger.

Therefore, the unit must be operated in non-condensing operating conditions.

HP 11642 1200mm Rack specifications

U height

Width

Depth

Dynamic load (gross)

Static load

42U

598 mm

(23.8 in)

1,300 mm

(47.24 in)

1,021 kg

(2,250 lb)

1,361 kg

(3,000 lb)