Installation 24

12.

(Optional, but HP-recommended) To set up your SNMP managers, click Setup>Management>SNMP
Managers.

13.

Click Save Settings.

For more information on adjusting the management module settings through the web interface, see the HP

Modular Cooling System Web Interface User Guide.

Connecting water to the facility

CAUTION:

Before attaching the hoses to the MCS-100 unit, verify that the water supply and

return are closed. Water that leaks into the unit can cause significant damage.

CAUTION:

Do not over tighten the connection. Tightening the connection too much might

damage the gaskets.

NOTE:

The MCS-100 unit is equipped with a failed-open control valve. For water to flow through

the unit without restrictions during the initial water hook up, HP recommends that the control valve

is set manually to Open through the web interface.