Management module components – HP Modular Cooling System User Manual
Page 30
Management module 30
•
Fan Module—Displays the Server Intake and Server Exhaust Temperature as well as the RPM of each
fan
•
Water Inlet Temperature—Displays the temperature of the water coming into the MCS-100 unit to be
used to cool the servers
•
Water Outlet Temperature—Displays the temperature of the water after removing the server heat
•
Water Flow—Displays the value of the water flow in liters/gallons per minute
Management module components
The management module is located on the lower front of the MCS-100 unit, behind the front door.
Item Reference
Description
1
C key
Used to confirm warnings, critical alarms, and
configuration setting changes, as well as to turn off the
audible alarm. To confirm these situations, press and
hold the C key for five seconds, or click the Clear Alarms
button on the Setup tab>General menu on the web
interface.
2
Power/alarm LED Used to indicate the internal status of the management
module, and to signal warnings and critical alarms.
•
If the LED is green, the management module has
power, and conditions are normal.
•
If the LED is green and blinking, communication is
taking place.
•
If the LED is yellow, a warning has been issued.
•
If the LED is red, a critical alarm has been issued.
•
If the LED is blinking green, yellow and red, then a
configuration setting change has been made. To save
the new configuration settings to the internal memory
of the management module, press and hold the C key
for five seconds.
•
If the LED is off, the management module has no
power.
3
Mini USB
connection
Used for USB connections for initial setup.