HP Modular Cooling System User Manual
Page 46
Operator display 46
1.
Verify the water supply.
2.
Contact HP, or see the HP website
Water flow valve is closed
Indicators
Meaning
Operator display alarm message Water Valve?
Web interface alarm message
Water Valve Failed
Condition
Water flow valve is closed, and water flow is detected.
Modules
Water group
SNMP notification
Warning
Type of message
Warning
Solution:
1.
Verify the water valve is closed.
2.
Contact HP, or see the HP website
Leak detector sensor is not working properly
Indicators
Meaning
Operator display alarm message Leak detector?
Web interface alarm message
Leak detector Failed
Condition
Leak detector sensor is not working properly.
Sensors
Leak detector sensor
SNMP notification
Warning
Type of message
Warning
Solution:
Contact HP, or see the HP website
Uneven heat load
Indicators
Meaning
Operator display alarm message Heat Load?
Web interface alarm message
Heat Load Warning
Condition
Measured air temperature values are dramatically different from top to
bottom.
Sensors
Air temperature sensors
SNMP notification
Warning
Type of message
Warning
Solution:
1.
Verify that nothing is blocking the heat path.
2.
Verify that the server is loading.
3.
Adjust the Temperature Difference for Heat Load Warning in the Advanced tab.
Heat overload condition (High Temperature Threshold field)