Required tools, Installing the mcs-100 – HP Modular Cooling System User Manual
Page 10
Installation 10
Item
Description
Quantity
3
T-25 bit socket
Allen key
1
1
4
Door/side panel key
2
5
Quarter turn hook and loop strap
10
6
Leveling pads
4
Extra hardware might be included for your convenience.
Required tools
The following tools are required for installation:
•
Flat blade screwdriver
•
#2 Phillips screwdriver
•
Adjustable wrench
•
T-25 Torx screwdriver
•
T-30 Torx screwdriver
•
Bubble level
•
Hose wrenches (2)
Installing the MCS-100
WARNING:
The MCS-100 unit and rack are shipped together on a heavy duty shock pallet
weighing approximately 1950 kg (4300 lb). HP recommends hiring professional movers to move
the heavy duty shock pallet, remove the MCS-100 unit and rack from the pallet, and move the
MCS-100 unit and rack to the final location.
CAUTION:
Contaminated water might cause decreased cooling capacity or disruption in
service. The water flowing into the MCS-100 unit must meet the guidelines stated in the HP
Modular Cooling System 200/100 Site Preparation Guide. The MCS-100 warranty does not
cover damage caused by contaminated water.
IMPORTANT:
Because the MCS-100 unit consumes a large quantity of water, do not operate the
MCS-100 unit from a public water system such as one that supplies drinking water. For water
conservation purposes, to cool the MCS-100 unit, use only recycled water systems.
IMPORTANT:
Before you begin the installation process, review the HP Modular Cooling System
200/100 Site Preparation Guide.
1.
Install the HP Modular Cooling System Hook Up Kit.
2.
Read the unpacking instructions on the MCS-100 packaging material.
3.
Using four or more people, remove the MCS-100 unit and rack from the pallet.
4.
Roll the MCS-100 unit and rack to the final location.
WARNING:
To avoid tipping the MCS-100 unit over, make sure the leveling feet are lowered
when the MCS-100 is equipped, serviced, and operated.