Specifications, Mcs-100 specifications – HP Modular Cooling System User Manual
Page 55
Specifications 55
Specifications
MCS-100 specifications
Item
Specification
Voltage
230 VAC +/- 10%, 50 Hz
Maximum height
(including the rack)
200.7 cm (79 in)
Maximum width
(including the rack)
90.4 cm (35.6 in) maximum
Maximum depth
(including the rack and
rack handle)
126 cm (49.6 in)
Maximum shipping
height (on skid)
228.5 cm (90.0 in)
Maximum shipping
width (on skid)
122.0 cm (48.0 in)
Maximum shipping
depth (on skid)
182.9 cm (72.0 in)
Net weight (including
the empty rack)
417 kg (919 lb)
Shipping Weight (gross
with packaging)
670 (1479 lb)
Effective cooling
30 kW at 50 l/min (13.2 US gal/min)
(L42W10, L20)
Rated current maximum 230 VAC - 18 Amps
Steady state current
with maximum fans
230 V - 7.7 Amps
Cooling medium
water
Prefuse
20A
Minimum
recommended water
inlet temperature
7°C (45°F)
Permissible operating
pressure pmax
8 bar (116 psi)
Maximum operating
noise level
79 dB(A)
NOTE:
The abbreviation L42W10, L20 is part of the type plate information and stands for hot air
temperature of 42°C (107°F), chilled water temperature of 10°C (50°F), and cold air temperature
of 20°C (68°F).