Water quality and leveling requirements, and condensation management 64

Parameter

Range

Sodium (Na)

0–1000 ppm

Silica (SiO

2

)

0–150 ppm

Zinc (Zn)

< 1.0 ppm

Manganese (Mn)

< 0.1 ppm

Phosphate Ortho- (Po

4

)

< 3 ppm

Bacteria

< 1000 CFU/ml

Suspended solids

< 10 ppm

If your water is out of range, consult a water quality expert.
HP recommends using particulate filtration on the dedicated water supply system connected to the MCS
5042 unit.

Frost damage

To avoid frost damage, the water temperature must not be allowed to fall below the minimum permissible
temperature of +4 ºC (+39.2 ºF) at any point in the water cycle.
Before storage or transportation at sub-zero temperatures, the water cycle must be drained completely using
compressed air. Avoid setting the target temperature lower than is necessary because the danger of falling

below the dew point increases as water temperature decreases (condensation buildup). Ensure that the
enclosure is sealed on all sides, and in particular at the cable inlet (condensation formation).

Water precautions

Take the following precautions during the installation of the MCS 5042 unit:

Before installing the HP mc-Series 5042 Rack Hook-Up Kit, ensure that all foreign matter and

particulates are flushed from the system.

Evaluate the short-term and long-term system requirements against the available water capacity.

Ensure that the chilled water loop is properly designed for liquid cooling systems and is separate from

the sanitary water systems in your building (bathroom, sink, drinking water, and so on).

Ensure facility managers understand the additional load being added to the chilled water supply of the

building. Be aware that the added heat load might affect other components being cooled by the chilled
water plant.

Plumbing materials to avoid

Do not use the following materials in a closed water system:

Oxidizing biocides

Aluminum components

Brass components with high levels of zinc

Non-stainless steel Iron components