HP Modular Cooling System User Manual
Page 13
Installation 13
WARNING:
To reduce the risk of electric shock or damage to the equipment:
•
Do not disable the power cord grounding plug. The grounding plug is an important safety
feature.
•
Plug the power cord into a grounded (earthed) electrical outlet that is easily accessible at all
times.
•
Unplug the power cord from the power supply to disconnect power to the equipment.
•
Do not route the power cord where it can be walked on or pinched by items placed against it.
Pay particular attention to the plug, electrical outlet, and the point where the cord extends from
the storage system.
1.
Plug the power cords into an appropriate power source.
2.
Connect the network cable to your network infrastructure.
NOTE:
If you have a DHCP server, you can change the IP address through the web interface
instead of through the serial port. For more information, refer to "Configuring the IP address
through the web interface."
3.
Using the serial cable provided, connect a PC with a serial port or an asynchronous terminal to the
serial communication port on the management module.
4.
Access the management module through a terminal emulation program, such as HyperTerminal
("
" on page
) or Minicom.
5.
Confirm that you have set the following parameters to access a terminal emulation program:
o
Bits per second: 9600
o
Data bits: 8
o
Parity: none
o
Stop bits: 1
o
Flow control: none
6.
Log in to the HP Modular Cooling System Configuration Utility:
a.
In the login field, enter the user name. The default user name is Admin.