Specifications, Mcs specifications – HP Modular Cooling System User Manual
Page 60
Specifications 60
Specifications
MCS specifications
Item
Specification
Voltage
208V 60Hz (UL); 230V 50Hz (CE, CB)
Maximum Height
(including the rack)
200.9 cm (79.1 in)
Maximum Width
(including the rack)
90.9 cm (35.8 in) maximum
Maximum Depth
(including the rack and
rack handle)
149.0 cm (59.0 in) (Depth includes rear extension)
Maximum Shipping
Height (on skid)
228.5 cm (90.0 in)
Maximum Shipping
Width (on skid)
122.0 cm (48.0 in)
Maximum Shipping
Depth (on skid)
182.9 cm (72.0 in)
Net Weight (including
the empty rack)
450 kg (992 lb) Weight includes rear extension which
weighs 30 kg (67 lb)
Shipping Weight (gross
with packaging)
704 kg (1552 lb) Weight includes rear extension which
weighs 30 kg (67 lb)
Effective cooling
50 kW at 124 l/min (32.8 US gal/min)
(L42W10, L20)
Rated current maximum 208 VAC–18 Amps
Cooling medium
water
Minimum
recommended water
inlet temperature
7°C (45°F)
Permissible operating
pressure pmax
8 bar (116 psi)
Maximum operating
noise level
79 dB(A)
NOTE:
The abbreviation L42W10, L20 is part of the type plate information and stands for hot air
temperature of 42°C (107°F), chilled water temperature of 10°C (50°F), and cold air temperature
of 20°C (68°F).