Connecting water to the facility – HP Modular Cooling System User Manual
Page 25
Installation 25
12.
(Optional, but HP-recommended) To set up your SNMP managers, click Setup>Management>SNMP
Managers.
13.
Click Save Settings.
For more information on adjusting the management module settings through the web interface, see the HP
mc-Series 5042 Rack Web Interface User Guide.
Connecting water to the facility
CAUTION:
Before attaching the hoses to the MCS 5042 unit, verify that the water supply and
return are closed. Water that leaks into the unit can cause significant damage.
CAUTION:
Do not over tighten the connection. Tightening the connection too much might
damage the gaskets.
NOTE:
The MCS 5042 unit is equipped with a failed-closed control valve that prevents water
from flowing through the unit when the unit is powered off. For water to flow through the unit
during the initial water hook up, the control valve must be manually set to Open through the web
interface.