Health—fault-tolerant fans, Health—temperatures – HP Remote Insight Lights-Out Edition II Board User Manual
Page 69

Using the software 69
Health—Fault-tolerant fans
This option displays the location, type, speed, and status of all redundant fans installed in the selected
server.
Health—Temperatures
This option displays environmental information from the HP Health Agent temperature sensor table.
The following threshold types might be displayed in the table:
•
Other (1)—Temperature threshold type could not be determined.
•
Blowout (5)—If a blowout (5) temperature sensor reaches its threshold, the fans in the area of the
temperature sensor increase in speed in an attempt to reduce the temperature before a caution or
critical threshold is reached.
•
Caution (9)—If a caution (9) temperature sensor reaches its threshold, the
cpqHeTemperatureCondition is set to degraded (3), and the system either continues or shuts down,
depending on the setting of cpqHeThermalDegradedAction.