SDAP Series PD 2 to PD 4 Drying and Conveying Systems
Figure 18
Setting List for Process Temperature Controller, Part No. A0548565
Mode Parameter
Setting
range Default
AEC setting
Protect SECr Security
0 to 6
1
5
Protect YEYP A/M Key Protect
ON/OFF
OFF
ON
Manual Manual MV
-5.0 to 105.0%
0.0
Default
Mode Parameter
Setting
range Default
AEC setting
Level 0 SP Set Point
SP Lower Limit to Upper Limit EU
0
Default
Level 0 r-S Run/Stop
Run/Stop
Run
Default
Level 1 SP-0 Set Point 0
SP Lower to Upper EU
0
Default
Level 1 SP-1 Set Point 1
SP Lower to Upper EU
0
Default
Level 1 AL-1 Alarm Value 1
-1999 to 9999 EU
0
25.0
Level 1 AL-2 Alarm Value 2
-1999 to 9999 EU
0
25.0
Level 1 AL-3 Alarm Value 3
-1999 to 9999 EU
0
Default
Level 1 P Proportional Band
0.1 to 999.9% FS
10.0
4.4
Level 1 I Integral Time
0 to 3999 SEC
233
84
Level 1 d Derivative Timer
0 to 3999 SEC
40
13
Level 1 C-SC Cooling Coefficient
0.01 to 99.99
1.00
Default
Level 1 C-db Dead Band
-19.99 to 99.99%FS
0.00
Default
Level 1 6F-r Manual Reset Value
0.0 to 100.0%
50.0
Default
Level 1 HYS Hysteresis (Heat)
0.01 to 99.99%FS
0.10
Default
Level 1 CHYS Hysteresis (Cool)
0.01 to 99.99%FS
0.10
Default
Level 1 CP Control Period (Heat)
1 to 99 SEC
20
Default
Level 1 C-CP Control Period (Cool) 1 to 99 SEC
20
Default
Mode Parameter
Setting
range
Default
AEC setting
Level 2 r-L Remote/Local
RMT/LCL
LCL
Default
Level 2 SPrU Sp Ramp Time Unit
M(Minutes)/H(Hours)
M
Default
Level 2 SPrE Sp Ramp Set Value
0 to 9999 EU
0
Default
Level 2 LbA LBA Detection Time
0 to 9999 SEC
0
Default
Level 2 Au-5 MV at Stop
-5.0 to 105.0%
0.0
Default
Level 2 Au-E MV at PV Error
-5.0 to 105.0%
0.0
Default
Level 2 6L-L MV Upper Limit
MV Lower Limit +0.1 to 105.0%
105.0
Default
Level 2 6L-L MV Lower Limit
-5.0 to MV Upper Limit –0.1%
-5.0
Default
Level 2 6rL MV Change Rate Limit
0.0 to 100.0%/SEC
0.0
Default
Level 2 CnF Input Digital Filter
0 to 9999 SEC
0
Default
Level 2 ALH1 Alarm 1 Hysteresis
0.01 to 99.99%
0.02
Default
Level 2 ALH2 Alarm 2 Hysteresis
0.01 to 99.99%
0.02
Default
Level 2 ALH3 Alarm 3 Hysteresis
0.01 to 99.99%
0.02
Default
Level 2 Cn5H Input Shift Upper Limit -199.9 to 999.9
°C
0.0 Default
Level 2 Cn5L Input Shift Lower Limit
-999.9 to 999.9
°C
0.0 Default