For each space, Primary Room or Secondary Room, this screen is used to define the alarm
setpoints. When the room is then set to Positive, Neutral, or Negative, the setpoints and con-
ditions configured here are in effect for alarm and warning conditions.
The SRCM has a great deal of flexibility to define alarm conditions. Alarms and warnings
can be configured for primary and secondary rooms, and for the door. Room display can
toggle between Primary and Secondary. The following table outlines what will occur in
terms of priority and display under normal and alarm conditions.
N=Normal; A=Alarm
Toggle
High Priority
Display
Text (Maxi-
mum eight
Background
Remarks
Primary
Pressure
Secondary
Pressure
Disabled
N
N
Normal
Green
Displays primary pressure
or secondary pressure based
on the selection
in the setup
display screen.
Disabled
N
A
Alarm
Red
Shows Alarm for second-
ary room if secondary room
is selected for the display.
If the pressure to display is
selected as Primary, display
switches to the secondary
room to show the alarm.
Disabled
N
A
Alarm
Red
Shows Alarm for second-
ary room if secondary room
is selected for display. If
the pressure to display is
selected as Primary, display
switches to the secondary
room to show the alarm.
Alarm Set Point
Alarm Matrix