beautypg.com

Setra System Model 204D User Manual

General information and installation

background image

Model 204 and 239 Series

PRESSURE TRANSDUCERS

Pressure Transducers (0 to 5 VDC output)

Model 204

Gauge, Absolute, and Vacuum Pressure

Model 204D

Wet/Dry Differential Pressure

Model 239

Differential Pressure

Pressure Transducers (4 to 20 mA output)

Model C204

Gauge, Absolute and Vacuum Pressure

Model C239

Differential Pressure

General Information and Installation ..................................................................................................1

Electrical Information for Standard 24 VDC

Excitation Pressure Transducers (nominal)........................................................................................3

Electrical Information for Optional ±15 VDC (±24 VDC)

Excitation Pressure Transducers (Option #: 621 and 622) ............................................................4

Electrical Information for 4 to 20 mA Pressure Transducers .......................................................4

Adjustments for Pressure Transducers and Transducers

Zero and Sensitivity ...................................................................................................................................5

Remote Control Instructions for Pressure Transducers.................................................................6

Installation Instructions for Multiple Hook-Up of 4-Wire

Pressure Transducers (24 VDC Excitation Units Only) ....................................................................7

Returning Products for Repair ...............................................................................................................8

Calibration Services ...................................................................................................................................8
EMC Certification ........................................................................................................................................8
Limited Warranty ........................................................................................................................................8

General Information and Installation

Your Setra transducer has been carefully calibrated before shipment to you, and it should

be handled with the same care given any precision instrument. Pressure range and

dimensions are reported on the applicable specifications bulletin.
Ambient Conditions
Do not submerge in liquids, use in ambient conditions corrosive to anodized aluminum,

subject to spray or dripping, or use in a high vibration environment. The transducer is

very slightly sensitive to acceleration in the pressure fitting axis (see applicable specifica-

tions bulletin for acceleration response specifications). Installation is recommended in

the vertical position, with the pressure port downward. This position minimizes damage

from drippage of pressure system piping.

LIMITED WARRANTY AND LIMITATION OF LIABILITY

SETRA warrants its products to be free from defects in materials and workmanship, subject to the following terms and conditions:

Without charge, SETRA will repair or replace products found to be defective in materials or workmanship within the warranty

period; provided that:

a) the product has not been subjected to abuse, neglect, accident, incorrect wiring not our own, improper installation or

servicing, or use in violation of instructions furnished by SETRA;

b) the product has not been repaired or altered by anyone except SETRA or its authorized service agencies;
c) the serial number or product code has not been removed, defaced, or otherwise changed; and
d) examination discloses, in the judgment of SETRA, the defect in materials or workmanship developed under normal instal-

lation, use and service;

e) SETRA is notified in advance of and the product is returned to SETRA transportation prepaid.

Unless otherwise specified in a manual or warranty card, or agreed to in a writing signed by a SETRA officer, SETRA pressure and

acceleration products shall be warranted for one year from date of sale.
The foregoing warranty is in lieu of all warranties, express, implied or statutory, including but not limited to, any implied warranty

of merchantability for a particular purpose.
SETRA’s liability for breach of warranty is limited to repair or replacement, or if the goods cannot be repaired or replaced, to a

refund of the purchase price. SETRA’s liability for all other breaches is limited to a refund of the purchase price. In no instance

shall SETRA be liable for incidental or consequential damages arising from a breach of warranty, or from the use or installation of

its products.
No representative or person is authorized to give any warranty other than as set out above or to assume for SETRA any other

liability in connection with the sale of its products.

159 Swanson Road, Boxborough, MA 01719-1304

1-800-257-3872, (978)263-1400

8

RETURNING PRODUCTS FOR REPAIR

Please contact Setra (1-800-257-3872, 978-263-1400) before returning unit for repair to review in-

formation relative to your application. Many times, only minor field adjustments may be necessary.
When returning a product to Setra, the material should be carefully packaged and shipped prepaid to:

Setra Systems, Inc.

159 Swanson Road

Boxborough, MA 01719-1304

Attn: Repair Department

To assure prompt handling, please supply the following information and include it inside the pack-

age of returned material:

1.

Name and phone number of person to contact.

2.

Shipping and billing instructions

3.

Full description of the malfunction.

4.

Identify any hazardous material used with product.

Notes: Please remove any pressure fittings and plumbing that you have installed and enclose any

required mating electrical connectors and wiring diagrams.

Allow approximately 3 weeks after receipt at Setra for the repair and return of the unit.

Non-warranty repairs will not be made without customer approval and a purchase order to cover

repair charges.

Calibration Services

Setra maintains a complete calibration facility that is traceable to the National Institute of Standards

& Technology (NIST). If you would like to recalibrate or recertify your Setra pressure transducers,

please call our Repair Department at 1-800-257-3872 (978-263-1400) for scheduling, cost and

turnaround estimates.

EMC CERTIFICATION

This product complies with EN61326 Electrical Equipment for Measurement, Control and Laboratory use – EMC Requirements for
Minimum Requirements and Industrial Locations. Special caution should be taken to meet Standard EN61000-4-5: 1995 Surge
Immunity if any of the following conditions apply to the installation: The product is installed outside; all or any part of the cable
is exposed to the outside; the cable is greater than 30 meters in length. In order to meet the Surge Immunity requirements, the
following conditions must be followed during installation:

1. Shielded cable must be used, and the shield must be tied to earth ground (not power supply ground) on at least one end

of the cable shield/drain wire. The shield must be maintained all the way from sensor to the power supply.

2. If unshielded cable is used, an earth grounded metal conduit fitting can be used to replace the shielded cable.
3. For a sensor with a metal body or enclosure, the body/enclosure must be grounded to earth. If a protective metal housing

is used, the metal housing should be grounded to earth

4. If a protective plastic housing is used, the housing must be able to withstand at least

2 KV from the housing to earth ground, without damaging the circuit.

SS0461REV

.H 02/18/2014

This manual is related to the following products: