If a hand held pillow push device is required the call point/reset unit should be
installed within 1 metre of the bedhead and an S/1631 Pillow push unit connected
to the Call In terminals as shown. The pillow push unit is normally supplied with 2
metres of two core cable, this can be extended on site using a wall mounted
junction box. It is best to avoid excessively long trailing cable. The edge of the call
point plate is notched out as a cable entry for the pillow push.

Up to three ceiling pull cords with re-assurance
LEDs can be connected to an S/1663 call
point/reset unit. Each re-assurance LED draws
approximately 15ma. The LED on the pull cord will

flash in sympathy with the green LED on the S/1663 call point. If more than
one is fitted then both the switch contacts and the LEDs should be connected
in parallel.
The +ve feed for the LED and the +ve feed for the switch COM are common
therefore a three core cable could be used if this would be more convenient.

90

90

2000

33

2000

45

Dimensions
(mm)

Dimensions (mm)

Dwg No:60010:7 Iss2 Page 2 Jul 09

+ve

-ve

E/Recall

L/Attend

CALL OUT

Call In

+ve

Reset In

-ve

+ve

LED

Late Attend
Timer

S/1663
Call Point

+ve

-ve

E/Recall

L/Attend

CALL OUT

Call In

+ve

Reset In

-ve

+ve

LED

Late Attend
Timer

S/1663
Call Point

+ve

-ve

E/Recall

L/Attend

CALL OUT

Call In

+ve

Reset In

-ve

+ve

LED

Late Attend
Timer

S/1663
Call Point

+ve

-ve

E/Recall

L/Attend

CALL OUT

Call In

+ve

Reset In

-ve

+ve

LED

Late Attend
Timer

S/1663
Call Point

N.O.
COM
N.C.

LED

+ve
-ve

Call Point with S/1600
Ceiling Pull Cord

Call Point with S/1631 Pillow Push

Call Point with S/1636 Overdoor Lights

S/1600

To further pull
cords if required

Overdoor or end of corridor indicators can be incorporated on the system if
required. A blocking diode is included in each overdoor light to enable a
group of overdoor lights to signal onto to an end of corridor light. If a voltage
is applied to unit A then both A & C will illuminate, if applied to unit B, then B
& C will illuminate. In this way the system can be configured as a follow the
lights
type of system to enable patrolling staff to respond without returning
to the panel to verify if any alarm conditions have occurred. Overdoor lights