Hoyles Aidalarm Battery Powered Disabled Toilet Alarm Kit User Manual
Hoyles electronic developments ltd, Use six core intruder alarm cable or similar, B p r
The AIDALARM is designed as a disabled person alarm system primarily
100mm above floor level. The second bangle should be set between 800
for use in WCs etc..It is designed to comply with BS8300 and the
and 1000mm above floor level.
requirements of the Disability Discrimination Act.
The Reset Button S1708A should be sited near the point of call and
should be mounted with the bottom edge between 800 and 1000mm
The AIDALARM A600B controller should be sited where staff are located
above floor level and a minimum of 350mm from any corner.
who can respond to an emergency call. It is powered by 6 x AA Alkaline
The Overdoor Light/Sounder S1778A is usually sited outside and above
batteries and there is an integral battery fault monitor. Being battery
the WC door.
powered the ancillary items in toilets or other wet areas are at a safe
DADO Panic Strip (Optional) is a normally open device, the contacts
working voltage avoiding any conflict with Part P building regulations.
close when the switch is pressed. Site 150mm from floor level in WCs.
The Pull Cord S1600 should be appropriately sited for your application in
the WC or where assistance is required. Additional pull cords if required
are available separately. The lower bangle on the cord should be set at
Battery Powered AIDALARM A600B Installation Instructions
Wiring details
Standard 6 core intruder alarm cable or similar is ideal to connect the AIDALARM controller to the ancillary items.
ve
+
A600B Controller
Located in responders
area
N.O
COM
N.C.
L+ve
L-ve
BZ1
L7
L8
R11
LED6
B
W Y
NC
NC
L5
L6
NO
COM
B
W Y
COM
NO
LED5
+
R8
ZD1
PB1
L1
P2
P1
BZ
Pull Cord S1600
Overdoor Light/Buzzer
S1778A
Located outside WC
Reset Button S1708A
Located inside WC
BZ1
L7
L8
R11
R12
R14
R7
R3
R5
R6
LED6
LED4
LED2
LED8
B
W Y
NC
NC
L5
L6
NO
COM
B
W Y
COM
NO
LED5
LED3
LED1
LED7
+
R8
ZD1
L1 L2
BZ
Use six core intruder
alarm cable or similar
DADO Panic Strips (optional)
021-485SE
Call
Com
Reset
SDR
-ve
LED
-ve
Fn
B P R
Battery
Connections
Set
Use
[
[
Set Button
PB1
PB2
60139 Iss 1 Sept 2011
T. 01744 886600 F. 01744 886607 E. [email protected] W. www.hoyles.com
Hoyles Electronic Developments Ltd
Operation
Reset buttons and Overdoor units are fitted with LEDs and buzzers. Pull Cords are fitted with an LED. Additional units can be fitted if required.
Battery Test
It is possible to test the batteries by pressing and holding the control p
illuminated indicates the
batteries are very low, three LEDs indicate that the batteries are partly discharged and four LEDs indicate that the batteries are healthy.
Using the factory default settings, when a call is generated by pulling the cord or by activating any optional call accessory such as panic strip, audible and
visual warning is given at both the WC area and at the AIDALARM control panel. The call can be silenced at the control panel by pressing the control panel
button which is located at the centre of the LED diamond. This will cause the panel to bleep every 40 seconds as a warning of non attendance by the
responders. The audible indicators at the WC will bleep every five seconds to re-assure the caller. Should the cord be pulled again while in the Silence
state, the system will call again. The system is reset at (or near) the point of call using the Reset button S1708A.
Silence
buttons S1703PR can also be fitted to give a more flexible operation. Consult our technical dept.
anel button at the centre of the LED diamond. One LED
Technical Features
Battery Monitoring
The control panel monitors the health of the batteries. When the batteries reach the end of their life, the control panel will beep and momentarily flash the
green power LED every 3 minutes. This prompts the system operator to have the batteries replaced. Good quality alkaline batteries should be used. It is
recommended that these batteries are replaced every 12 months during a regular maintenance inspection.
3 x AA
Batteries
3 x AA
Batteries