beautypg.com

Hoyles Six Zone Assistance Call Panel for Toilet or Pool Alarms User Manual

Hoyles electronic developments ltd, Wiring for pool alarm system, Wrp-b-11

background image

The system components for a toilet system The system components for a pool alarm system
AA31110D Controller

AA31110D Controller

S1600 Non-latching Pull Cords with LEDs or

WRP-B-11 Latching waterproof call points or

S1705P Non-latching Call buttons with LEDs

S1711WP Latching twist to reset call buttons

S1708PR Reset buttons or

8581750/HB Sounder beacon

S1708S Stainless Steel Reset Buttons

LAB35200 Call point signs

S1778PR Overdoor Light/buzzer or
S1778SR S/ Steel Overdoor Light/buzzer

Z1

Z2

Z3

Z4

Z5

Z6

F3

MULTIGUARD 2000 - 6

197

138

72

Dimensions (mm)

MULTIGUARD AIDALARM AA31110D

INSTALLATION INSTRUCTIONS

IT IS IMPORTANT TO FIX THE

Connection & Power Up se-

MULTIGUARD TO A FLAT quence.
S U R F A C E . I F T H E B O X
The MULTIGUARD has a short

DISTORTS IT IS DIFFICULT TO

test or verification sequence on

C L I P T H E V A R I O U S power up. You should verify that

COMPONENTS TOGETHER

the unit as supplied is function-

T O F O R M A S E C U R E ing normally before making any

HOUSING.

connections.

Cables may enter through the

1. Ensure F4 is linked to +ve.

20mm holes in the rear of the

& Yellow) and earth lead (Green)

Plug in the battery. The plug is

box or through the entry slots lo-

are connected to the PCB.

polarised to maintain the correct

cated on each side. As the

polarity. The integral sounder

4. Reconnect the battery, the sys-

mains power cable is generally

will beep at 1 second intervals.

tem will once again go through

the largest it should be routed

Press the SILENCE button F1.

the test routine. Clip the PCB as-

into the central compartment

The LED's will flash three times

sembly onto the back box.

and dressed in for connection to

and then reset automatically.

4. Switch on the power at the

the fused terminal before dress-

Disconnect the battery.

fused spur. Observe the green

i n g i n t h e l o w v o l t a g e

2. Dress the cables into the ca-

Mains On LED.

cables.Low voltage cables

ble channel, trim to length and

6. The system can now be tested

should be routed into the cable

terminate as per the connection

and the decal marked up and lid

channel between the inner and

diagram. Any excess cable

clipped into place.The mark re-

outer walls of the box. These ca-

should be left in the side chan-

sistant decal covers a remov-

bles should only be cut to length

nels between the clip and the

able identification panel which

when you are ready to terminate

outer wall. This helps to prevent

can be created by a word pro-

them on the PCB assembly. Be

the clips deforming.

cessor or graphics package to

sure to leave enough length to al-

3. Connect the mains cable from

enable a professional looking fa-

low the PCB assembly to be re-

a suitable fused spur to the Live,

cia to be achieved for each in-

moved for access to the fuses

Neu tra l & E art h te rmi nal s. stallation. Two example blanks

and battery terminals at a later

Ensure the mains fuse is fitted

are supplied with these instruc-

stage.

and the transformer leads (Blue

tions.

Strobe Sounder Strobe

-ve -ve +ve +ve

8581750/HB

1 2 3 4 5 6 7 8 9

Zones 1-6 for

buzzer outputs

Strobe Sounder Strobe

-ve -ve +ve +ve

- + 1 2 3 4 5 6 + + 1 2 3 4 5 6 + + 1 2 3 4 + -

8581750/HB

INPUTS

- + X S D C

Zones 1-6 for

LED outputs

SERIAL

OUTPUT

10 11 12 13 14 15 16

-ve +ve

ZONE RESETS

RELAY

OUTPUT

B

lu

e

Wiring for Pool Alarm system

N

O

C

O

M

N

C

W

h

it

e

WRP-B-11

FUNCTION

INPUTS

Y

e

llo

w

S1711WP

AA31110D
Complies with Council
Directive 89/336/EEC

AA31110D

+ve 12vdc can be taken from
any +ve terminal on the pcb
they are all common

Mains Fuse

F4 must be linked to +ve
to use normally open
switch inputs

Dwg No:60060 Iss 4 November 2012

N
E
L

16vac
Input

T. 01744 886600 F. 01744 886607 E. [email protected] W. www.hoyles.com

Hoyles Electronic Developments Ltd

GENERAL
The AA31110D is designed to give audible and visual re-assurance indication at the point of operation.
Non latching (toilet alarm) and latching (pool alarm) devices can be used on the same controller. The
software deems that any alarm input for less than 5 seconds is a non latched input, therefore a disabled
toilet alarm signal and any alarm signal longer than 5 seconds is latched, therefore a pool alarm signal.
when latching buttons are used the MULTIGUARD will reset when the call point is reset. Separate reset
buttons are therefore not required for pool alarms.

OPERATION.
When a call point is operated the local indicators and buzzers operate to inform the caller that the call has
been transmitted. The zone LED at the panel also flashes and the integral buzzer sounds. The global alarm
relay switches while the buzzer sounds. When a call is silenced at the panel all flashing LEDs becomes
steady and all buzzers silence to inform everyone involved, that the call has been received and help is on
the way. When help finally arrives the call is reset at the point of activation. All LEDs and buzzers pertaining
to that zone will be extinguished and silenced. (If a toilet alarm input is seen by the panel after the zone has
been silenced, the zone will re-trip).
POWER SUPPLY
The AA31110D is supplied with an integral 13.8vdc power supply rated at 250ma with a rechargeable 0.7
Ahr standby battery. The MULTIGUARD has a power requirement of 25ma quiescent and 60ma maximum
with all zones tripped. The integral power supply will therefore support six zones plus the external ancilliary
equipment such as over door lights and buzzers. However, it will not support all zones tripped for long
periods. The standby battery will support the system for about six to eight hours in quiescent and
approximately 3 hours if two zones are tripped.

Note
X D C
gives steady output
to drive strobes

Table of contents