The AIDALARM is designed as a disabled person alarm The Pull Cord S1600 should be appropriately sited for your
system primarily for use in WCs etc..It is designed to comply

application in the WC or where assistance is required.

with BS 8300 an d the re quirem ents of t he Disa bility Additional

pull

cords

if

required

are

available

separately.

The

Discrimination Act.

lower bangle on the cord should be set at 100mm above floor
level. The second bangle should be set between 800 and

The AIDALARM A600F controller should be sited where staff

1000mm above floor level.

are located who can respond to an emergency call. It needs to

The Reset Button S1708SR should be sited near the point of

be powered by a 12vdc power supply (available separately)

call and should be mounted with the bottom edge between 800

which should have a standby battery fitted. The power supply

and 1000mm above floor level and a minimum of 350mm from

should be rated at a minimum of 250mA. See part numbers

any corner.

PSU-12/1A5B and BAT12V3300LA. The system voltage is

The Overdoor Light/Sounder S1778SR is usually sited

12vdc thus the ancillary items in toilets or other wet areas are at

outside and above the WC door.

a safe working voltage avoiding any conflict with Part P building

DADO Panic Strip (Optional) is a normally open device, the

regulations.

contacts close when the switch is pressed. Site 150mm from
floor level in WCs.

12vdc Powered AIDALARM A600F Stainless Steel Installation Instructions

Wiring details
Standard 6 core intruder alarm cable or similar is ideal to connect the AIDALARM controller to the ancillary items.

60130 Iss 1 June 2011

T. 01744 886600 F. 01744 886607 E. [email protected] W. www.hoyles.com

Hoyles Electronic Developments Ltd

Operation

Overdoor units are fitted with LEDs and buzzers. Pull Cords are fitted with an LED. Additional units can be fitted if required. Call
buttons S1705SR can also be fitted to give a more flexible operation. Consult our technical dept.

Using the factory default settings, when a call is generated by pulling the cord or by activating any optional call accessory such as
panic strip, audible and visual warning is given at both the WC area and at the AIDALARM control panel. The call can be silenced
at the control panel by pressing the control panel button. This will cause the panel to bleep every 40 seconds as a warning of non
attendance by the responders. The audible indicator at the WC will bleep every five seconds to re-assure the caller. Should the
cord be pulled again while in the Silence state, the system will call again. The system is reset at (or near) the point of call using the
Reset button S1708SR.

Alarm Relay
A single pole change over volt free relay is provided in the control panel. This relay is energised while the system is in its idle state,
when a call is made the relay de-energises, the relay energises again once the call has been reset. The relay also de-energises if
the 12dvc power is lost..

N

O

C

O

M

N

C

B

lu

e

Y

e

llo

w

W

h

it

e

ve

-

ve

+

ve

+

A600F Controller

Located in responders
area

N.O

COM

N.C.

L+ve

L-ve

Pull Cord S1600

Overdoor Light/Buzzer
S1778SR
Located outside WC

Reset Button S1708SR
Located inside WC

Use six core intruder
alarm cable or similar

DADO Panic Strips (optional)

021-485SE

NO

Com

NC

Call

Com

Reset

SDR

-ve

LED

-ve

Fn

Set

Use

[

[

Set Button

Call LED

Power LED

-ve

+ve

-ve

+ve

12vdc input from a

12vdc power supply.

Volt free auxiliary
relay contacts
change on alarm
and mains fail