Dwyer 1600 User Manual
Page 32

949-1239-3
32
Rev. 10/98
3 - SP1 on Output B & reverse acting, and SP2 on Output A & direct acting
4 - SP1 on Output A & direct acting, and SP2 on Output B & reverse acting
5 - SP1 on Output B & direct acting, and SP2 on Output A & reverse acting
6 - SP1 on Output A & reverse acting, and SP2 on Output B & reverse acting
7 - SP1 on Output B & reverse acting, and SP2 on Output A & reverse acting
8 - SP1 on Output A & direct acting, and SP2 on Output B & direct acting
9 - SP1 on Output B & direct acting, and SP2 on Output A & direct acting
Factory default for single set point units is 0. Factory default for dual set
point units is 2.
If Hrd1 = 0 you may skip steps 8 - 10. Press INDEX three times to
proceed to step 11, ACPt.
If Hrd1 = 1 then continue with step 8.
8.
Press INDEX to CnF4. Select the desired alarm type from the following
list:
0 - No Alarm (This may be selected even if Hrd1 = 1)
1 - High Alarm, Absolute Setting
2 - High Alarm, Deviation Setting from SP1
3 - Low Alarm, Absolute Setting
4 - Low Alarm, Deviation Setting from SP1
5 - High and Low Alarm, Absolute Settings
6 - High and Low Alarm, Deviation Settings from SP1
Factory default is 0 if Hrd1 = 0, 1 if Hrd1 = 1.
9.
Press INDEX to CnF5. Select the desired alarm action from the
following list:
0 - No Alarm
1 - Alarm acts as on/off output
2 - Alarm requires manual reset & has power interrupt feature on
3 - Alarm requires manual reset & has power interrupt feature off
4 - Alarm acts as on/off output & has inhibit feature
5 - Alarm requires manual reset and has inhibit feature
Factory default is 0 if Hrd1 = 0, 1 if Hrd1 = 1.
10. Press INDEX to CnF6. Select the alarm relay state from the following
list:
0 - No Alarm
1 - Alarm relay closes at the alarm point, alarm lamp flashes
2 - Alarm relay opens at the alarm point, alarm lamp flashes
3 - Alarm relay closes at the alarm point, alarm lamp is off
4 - Alarm relay opens at the alarm point, alarm lamp is off
Factory default is 0 if Hrd1 = 0, 1 if Hrd1 = 1.
11. Press INDEX to AcPt. If you do not want to retain the re-configuration,
this is your last chance to return to the old configuration. Press ENTER
at AcPt no to exit and retain the old configuration. Otherwise, press UP
ARROW and ENTER at AcPt YES to retain the new configuration.
12. Press INDEX to id. This display shows the version code for the software
in the instrument. If you believe that the control is not performing