3.

Press the INDEX key to advance to the next menu item, Hrd2. Press the
UP ARROW until the upper display shows the number code for Output
A (Set Point 1). Acceptable values are 1, 2, 3, and 4 (for 5 VDC,
mechanical relay, and SSR outputs); 5 (for proportional current output);
or 6 (for proportional voltage output). Press ENTER.

3.

Press INDEX to Hrd3. If your instrument is equipped with an optional
second set point (Output B, Set Point 2), press the UP ARROW key to
select the desired value. Acceptable values are 0 (no Output B), 1, 2,
3, and 4 (for 5 VDC, mechanical relay, and SSR outputs). Press
ENTER.

4.

Press INDEX to OPT1. If your instrument is equipped with an option,
press the UP ARROW or DOWN ARROW as necessary to display the
option number. The option number will be flashing. To select the option,
press ENTER while the option number is displayed. When selected, the
option number will stop flashing. DO NOT SELECT AN OPTION IF THE
INSTRUMENT DOES NOT HAVE THE HARDWARE TO SUPPORT
IT. SELECTION OF AN UNSUPPORTED OPTION MAY CAUSE
IMPROPER OPERATION OF THE INSTRUMENT.

6.

If you wish to program the menu pre-sets (configuration), press INDEX
to CnF1. To preset the input type press the UP Arrow or DOWN
ARROW for the following selections:
01 - Type J, whole degree

14 - Type S, whole degree

02 - Type J, tenth degree

15 - Type B, whole degree

03 - Type K, whole degree

16 - Type C, whole degree

04 - Type K, tenth degree

17 - DIN RTD, whole degree

05 - Type E, whole degree

18 - DIN RTD, tenth degree

06 - Type E, tenth degree

19 - NIST RTD, whole degree

07 - Type T, whole degree

20 - NIST RTD, tenth degree

08 - Type T, tenth degree

21 - Ni RTD, whole degree

09 - Type L whole degree

22 - NI RTD, tenth degree

10 - Type L, tenth degree

23 - 0 to 20 mA

11 - Type N whole degree

24 - 4 to 20 mA

12 - Type N, tenth degree

25 - 0 to 5 V

13 - Type R, whole degree

26 - 1 to 5 V

Factory default is 01 - Type J, whole degree.

6.

Press INDEX to CnF2. If CnF1 is equal to 01 through 22, press UP
ARROW to select 1 for degrees F or 2 for degrees C. If CnF1 is equal
to 23 through 26, press UP ARROW to select 0 for no descriptor, 1 for
degrees F, or 2 for degrees C. Factory default is 1, degrees F.

7.

Press INDEX to CnF3. Press UP ARROW to select one of the following:
(if Hrd3 = 0)
0 - SP1 is on Output A and is reverse acting
1 - SP1 is on Output A and is direct acting
(If Hrd3

0)

2 - SP1 on Output A & reverse acting, and SP2 on Output B & direct acting