Dwyer 1600 User Manual

Page 26

background image

949-1239-3

26

Rev. 10/98

ALt

Alarm Type: Select AbS or dE
AbS

Absolute Alarm that may be set anywhere within the
values of SPL and SPH and is independent of SP1.

dE

Deviation Alarm that may be set as an offset from SP1.
As SP1 is changed the Alarm Point will track with SP1.

ALrE

Alarm Reset: Select OnOF or Hold.
OnOF

Automatic Reset.

Hold

Manual Reset. Acknowledge by simultaneously press-
ing the INDEX & DOWN ARROW keys for 5 sec.

ALPi

Alarm Power Interrupt: Select On or OFF.
On

Alarm Power Interrupt is ON.

OFF

Alarm Power Interrupt is OFF.

ALiH

Alarm Inhibit: Select On or OFF.
On

Alarm Inhibit is ON. Alarm action is suspended until the
process value first enters a non-alarm condition.

OFF

Alarm Inhibit is OFF.

ALSt

Alarm Output State: Select CLOS or OPEn.
CLOS

Closes Contacts at Alarm Set Point.

OPEn

Opens Contacts at Alarm Set Point.

ALLP

Alarm Lamp: Select O on or OoFF.
O on

Alarm Lamp is ON when alarm contact is closed.

OoFF

Alarm Lamp is OFF when alarm contact is closed.

ALbr

Alarm Loop Break: Select On or OFF.
On

Loop Break Condition will cause an Alarm Condition.

OFF

Loop Break will not affect the Alarm Condition.

The following Secure menu items apply only to Options. They may not
appear in your control.

SPSA

Set Point Select Action (948): Select rE or Int.
rE

Remote (external) selection of active set point value.

Int

Internal selective of active set point value.

Addr

Control Address (992): Set from 1 to FF. This number (hexadeci-
mal, base 16) must match the address number used by the host
computer.