CFSP

Communications Fail Set Point (992): Set to desired value.

Addr

Control Address (992): Set from 1 to FF. This number (hexadeci-
mal, base 16) must match the address number used by the host
computer. Viewed only in this menu.

SECURE MENU

Hold UP ARROW & ENTER for 5 Seconds. Press INDEX to change the
lower display. Press UP ARROW or DOWN ARROW to change the value
in the upper display.

SECr

Security Code: See the Security Level Selection and the Pass-
word Table in this manual, in order to enter the correct password.

InP

Input Type: Select one of the following. The Inputs are based on
four different groups; Thermocouples, RTD’s, Current, and Volt-
age. If changing from one of these groups, the DIP switch on the
A/D circuit board will have to be changed to match that particular
group. Refer to the Input wiring section for the proper switch
settings.

J-IC

Type “J” Thermocouple

CA

Type “K” Thermocouple

E-

Type “E” Thermocouple

t-

Type “T” Thermocouple

L-

Type “L” Thermocouple

n-

Type “N” Thermocouple

r-13

Type “R” Thermocouple

S-10 Type “S” Thermocouple
b-

Type “B” Thermocouple

C-

Type “C” Thermocouple

P392 100 ohm Platinum (NIST 0.00392

/

/°C), Love

Cal. 104.

n120 120 ohm Nickel, Love Cal. 105.
P385 100 ohm Platinum (DIN 0.00385

/

/°C), Love Cal.

106.

Curr DC Current Input 0.0 to 20.0 or 4.0 to 20.0 milliam-

peres.

UoLt DC Voltage Input 0.0 to 5.0 or 1.0 to 5.0 volts.
- - - -

Reserved

OSUP

Zero Suppression: Select On or OFF. Only with Current and
Voltage input types.
OFF

The input range will start at 0 (zero) Input.

On

The input range will start at 4.00 mA or 1.00 V.