The following diagram shows the action and reset functions for both
absolute and deviation alarms.

When “Alarm Power Interrupt” ALPi is programmed ON and “Alarm Reset”
is programmed for Hold, the alarm will automatically reset upon a power
failure and subsequent restoration if no alarm condition is present.

If “Alarm Inhibit” ALiH is selected ON, an alarm condition is suspended upon
power up until the process value passes through the alarm set point once.
Alarm inhibit can be restored as if a power up took place by pressing
together the INDEX and ENTER keys for 5 seconds.

W

ARNING

: I

F

INHIBIT

IS

ON

AND

A

POWER

FAILURE

OCCURS

DURING

A

HIGH

ALARM

,

RESTORATION

OF

POWER

WILL

NOT

CAUSE

THE

ALARM

TO

OCCUR

IF

THE

PROCESS

VALUE

DOES

NOT

FIRST

DROP

BELOW

THE

HIGH

ALARM

SETTING

. D

O

NOT

USE

THE

A

LARM

I

NHIBIT

FEATURE

IF

A

HAZARD

IS

CREATED

BY

THIS

ACTION

. B

E

SURE

TO

TEST

ALL

COMBINATIONS

OF

HIGH

AND

LOW

ALARM

INHIBIT

ACTIONS

BEFORE

PLACING

CONTROL

INTO

OPERATION

.

The following Secure menu items apply only to the alarm.

AL

Alarms: Select OFF, Lo, Hi, or HiLo.
OFF

Alarms are turned OFF. No Alarm menu items appear
in the Secondary and Secure menus.

Lo

Low Alarm Only. ALLo appears in the Secondary Menu.

Hi

High Alarm Only. ALHi appears in the Secondary Menu.

HiLo

High and Low Alarms. Both share the same Alarm Relay
output.

OFF

ON

OFF

ON

ON

OFF

ON

OFF

D

ALLo

ALHi

D

D

D

ALLo

ALHi

SP1

SP1

SP1

High Alarm

Low Alarm

High and Low Alarm

DEVIATION ALARMS

OFF

ON

OFF

ON

ON

OFF

ON

OFF

D

ALLo

ALHi

D

D

D

ALLo

ALHi

ABSOLUTE ALARMS