Display

The display (3) shows the text with the main operating information.

In the absence of control signals, after four minutes the display

reverts to the initial page.

General functions

Display

The regulator is equipped with a display to read and program the

control parameters, such as cut-in temperatures, function

activation delay times, thermal disinfection programs, solar system

control, etc. All the system’s functional parameters can be

configured to match individual requirements by means of the

“Select” knob and the three function keys.

Block protection function “Block Protect.”

When it is powered on, the regulator performs an initial check,

activating the valves and pumps to which it is connected. The

message “Block Protect.” appears on the display.

Pump and diverter valve anti-clog function

To prevent clogging of the pumps and diverter valves due to

prolonged stoppages, the regulator activates them for 60 seconds

after each period of 24 consecutive hours of disuse.

Frost protection

When the solid fuel generator flow temperature reaches a minimum

user-settable value, the regulator activates the primary side pump

to prevent the circuit from freezing.

Anti-legionella function (programs 5 and 8 only)

The regulator keeps the domestic water storage at the minimum set

temperature and raises the temperature in order to perform thermal

disinfection in accordance with customizable times.

Instantaneous domestic hot water production (programs 6 and
9 only)

The regulator manages the instantaneous domestic hot water

production by means of a second heat exchanger and, if

necessary, it sends the water to the boiler for thermal integration by

means of the (optional) SOLARINCAL kit (code 265359).

Overtemperature safety function

The regulator is equipped with a solid fuel generator

overtemperature monitoring function.

When the user-settable emergency temperature is reached on the

solid fuel generator, the regulator generates an alarm signal and

starts the pumps to dissipate the excess heat to the system or to an

emergency user service. This latter function can be activated by

means of a specific menu item. In this case, it is necessary to install

a diverter valve, driven by the regulator, to transfer the flow to the

emergency user service.

Probe control
Solid fuel generator flow temperature sensor error

When the working temperature range detected is below 0°C or

above 110°C, the following status is activated automatically: pumps

OFF, while the display shows the message “probe error” and the

LED flashes green and red alternately.

Select knob and function keys

LED

The LED (1) gives status information by means of a multicoloured

diode:
- flashing green:

regulator initialisation

- steady green:

regulator operating

- flashing green/red:

regulator operating with probe error or alarm

- flashing red:

regulator checking loop

- steady red:

regulator error.

Control description

1- Operating status indicator LED.

2- Mini DIN connector on front of panel for PC connection.

3- Menu display.

4- Select knob: selection of functions menu and parameter editing.

5- Function keys

5

-

+

Optimiser

1

2

3

4

Display and commands

Select knob

(4): can be rotated or pressed

Turn

the Select knob clockwise or

anticlockwise to select the options of the

function menu or to modify the values of the

various user-settable parameters.

Press

the Select knob to open the submenu

relative to the selected option.

Function keys

(5): can be pressed

Esc:

change the display of the selected menu

point and return to the previous menu level

Info:

displays brief information on the current

menu point

Set:

executes the change, confirming the

selected parameter value

-

+

-

-

-

To set parameters use the document

“MENU LIST” code 28180 supplied in the pack