Operating principle

The 1522 series regulator automatically manages a system composed of a solid fuel generator, integration gas boiler and tank-in-tank direct

inertial water storage combined with a solar system.

On the request of the adjustment thermostat TR (not supplied in the pack) located on the water storage, the regulator activates the solid fuel

generator using contact K (for generators that can be activated electrically).

When the minimum working temperature of the solid fuel generator has been reached (as detected by probe S1), the regulator starts pump P1,

diverts valve V1 to connect the heat exchanger to the system and starts pump P2. With the solid fuel generator off or not yet at working

temperature, the regulator starts the integration boiler by means of contact C, stopping pumps P1 and P2 and diverting diverter valve V1 to the

boiler.

In the case of solid fuel generator overtemperature, the regulator sends the flow rate of the secondary circuit either to the water storage (in the

presence of a demand from adjustment thermostat TR) or to an optional dissipation system, if present.

The regulator allows to manage a simple solar thermal circuit connected to the lower coil of the tank-in-tank inertial water storage.

When the minimum working temperature of the solar collector is reached, temperature difference ΔT is checked between probe Sol1 on the

solar collector and probe Sol2 on the lower section of the tank-in-tank water storage: if higher than the set value, solar circuit pump Psol is

started. Pump Psol continues to run for a selectable minimum time period and it stops if ΔT falls below the set value or when the set temperature

for the tank-in-tank inertial water storage is reached.

The regulator manages possible overtemperatures of the solar collector by starting pump Psol to dissipate the excess heat.

Optional

dissipator

Closed vessel

Open vessel

Sol 1

Psol

Sol 2

Heating system

SOLID FUEL

GENERATOR

SOLID FUEL

GENERATOR

DIRECT

TANK IN TANK

INERTIAL WATER STORAGE

HEATING

BOILER

Wiring diagram

L Live

L’ Live jumper

N Neutral

1 ON pump P1

2 ON pump P2

3’ Gas generator C

3 Gas generator C

4 ON diverter valve V1

5

NO

ON diverter valve V4

to optional dissipator

5

NC

6’ Solid fuel generator K

6 Solid fuel generator K

10 ON solar circuit pump Psol

y1 Probe S1

y2 Probe S1

y5 Solar water storage

probe Sol2

y6 Solar water storage

probe Sol2

y7 Solar collector

probe Sol1

y8 Solar collector

probe Sol1

x2 Adjustable thermostat

TR contact

x3 Adjustable thermostat

TR contact

S

Sol 2

Sol 1

Psol

wiring to be made

N Neutral common

N Neutral common

ON

1 2 3 4

Program 7 (software code PR86)

Heating with direct inertial water storage with tank-in-tank domestic hot water production, solar system

Number of probes utilised: 3

Probe S1 located on solid fuel generator flow

Probe Sol1 (not supplied in the pack) located on the solar collector

Probe Sol2 located on the tank-in-tank water storage