beautypg.com

C ω °c ω – Caleffi 1522 User Manual

Page 3

background image

3

CAUTION

Install Pt1000 probe, with red silicone sheath cable (Tmax 180°C), on the solar collector.

Dimensions

Probe connection
The cable connecting probes to the regulator must be
installed in a dedicated raceway. If the connection
cable shares the raceway with other power cables, an
earthed shielded cable must be used.
Any alteration to the wiring of the regulator could
result in electrical disturbance.
After performing work on the wiring, the regulator
must be reset by cutting off the electric supply for a
few seconds. Cable length can be increased to 100 m
using a 1 mm

2

cross section cable.

*The use of the probes is specified in the “Available programs” heading on page 5.

NTC probes* resistance table: for solid fuel generator flow, domestic water storage, domestic heat exchanger, inertial water
storage in parallel on the heating system, solar water storage.

Pt1000 probe* resistance table: for solar collector.

100

23

1/2”

ø

6,4

A

C

B

6

50

3

L (m)

B

A

A

B

6

28

2

L (m)

B

A

A

B

1,5

30

55

9

11

L (m)

B

A

C

D

D

43

17

1/4”

ø

6,4

C

B

A

°C

Ω

°C

Ω

-10

961

65

1252

-5

980

70

1271

0

1000

75

1290

5

1019

80

1309

10

1039

85

1328

15

1058

90

1347

20

1078

95

1366

25

1097

100

1385

30

1117

105

1404

35

1136

110

1423

40

1155

115

1442

45

1175

120

1461

50

1194

140

1536

55

1213

160

1611

60

1232

170

°C

-20
-18
-16
-14
-12
-10

-8
-6
-4

Ω

14616
13211
11958
10839

9838
8941
8132
7405
6752

°C

-2

±0
+2
+4
+6
+8

+10
+12
+14

Ω

6164
5634
5155
4721
4329
3974
3652
3360
3094

°C

+16
+18
+20
+22
+24
+26
+28
+30
+32

Ω

2852
2632
2431
2247
2079
1925
1785
1657
1539

°C

+34
+36
+38
+40
+42
+44
+46
+48
+50

Ω

1430
1331
1239
1154
1076
1004

938
876
819

°C

+52
+54
+56
+58
+60
+62
+64
+66
+68

Ω

767
718
673
631
592
556
522
491
462

°C

+70
+72
+74
+76
+78
+80
+82
+84
+86

Ω

434
409
386
364
343
324
306
290
274

°C

+88
+90
+92
+94
+96
+98

+100

Ω

260
246
233
221
210
199
189

Probe

Type

Supply

Standard application

Optional application

S1*

NTC

series

probe + contact probe holder:

code 150009

immersion pocket code 150029

S2*

NTC

optional

-

probe code 150006 + pocket code 257004

S3*

NTC

optional

-

probe code 150006 + pocket code 150029

S4*

NTC

series

probe code 150006 +

pocket code 257004

-

S5*

NTC

series

probe + contact probe holder:

code 150009

-

Sol2*

NTC

optional

-

probe code 150006 + pocket code 257004

Sol1*

Pt1000

optional

-

immersion type: probe code 257006 +

pocket code 257004

NTC probe and contact probe
holder code 150009

Immersion pocket
code 150029

NTC probe
code 150006

Pt1000 probe
code 257006

Immersion pocket
code 257004

Relay box
code F29525

See instruction sheet,
code 28134