Safety test 44, Technical data, Environmental conditions – West Control Solutions D280-1 User Manual
Page 44: Allgemeines
Protocol:
Modbus RTU
Transmission speed: 2400, 4800, 9600, 19.200 bits/sec
Address range:
1...247
Number of controllers per bus:
32
Repeaters must be used to connect a higher number of
controllers.
ENVIRONMENTAL CONDITIONS
Protection modes
Front panel:
IP 65
Housing:
IP 20
Terminals:
IP 00
Permissible temperatures
For specified accuracy:
0...60°C
Warm-up time:
³ 15 minutes
For operation:
-20...65°C
For storage:
-40...70°C
Humidity
75% yearly average, no condensation
Shock and vibration
Vibration test Fc (DIN 68-2-6)
Frequency:
10...150 Hz
Unit in operation:
1g or 0,075 mm
Unit not in operation:
2g or 0,15 mm
Shock test Ea (DIN IEC 68-2-27)
Shock:
15g
Duration:
11ms
Electromagnetic compatibility
Complies with EN 61 326-1
(for continuous, non-attended operation)
ALLGEMEINES
Housing
Material:
Makrolon 9415 flame-retardant
Flammability class:
UL 94 VO, self-extinguishing
Plug-in module, inserted from the front
Safety test
Complies with EN 61010-1 (VDE 0411-1):
Overvoltage category II
Contamination class 2
Working voltage range 300 V
Protection class II
cUL certification
(Type 1, indoor use)
File: E 208286
Electrical connections
Screw terminals for 0,5 to 2,5 mm²
Mounting
Panel mounting with two fixing clamps at
top/bottom or right/left,
High-density mounting possible
Mounting position:
uncritical
Weight:
0,27kg
Accessories delivered with the unit
Operating manual
Fixing clamps
Technical data
Digital 280-1
44