beautypg.com

2 configuration 24, Configuration-parameter 24 - 29, Configuration 24 – West Control Solutions D280-1 User Manual

Page 24: Func, 2 configuration

background image

5.2 Configuration

Dependent of instrument version and configuration, spare parameters are not dis-
played.

Func

name

value range

description

default

Fnc.1

function 1

0

0

no function

1

tare - function

2

sample & hold

3

O2 - measuring

Fnc.2

function 2

0

0

indicator

1

controller

C.Fnc

controller behavior (algorithm)

1

0

on/off controller e.g. signaller with one output

1

PID-controller (2-point and continuous)

C.Act

operating principle of the controller

0

0

inverse, e.g. heating

1

direct, e.g. cooling

rnG.L

-19999...99999

X0 (lower controlrange limit) 1

-100

rnG.H

-19999...99999

X100 (upper controlrange limit) 1

1200

1 rnG.L and rnG.H indicate the control range to which self-tuning refers.

InP

name

value range description

default

S.tYP

sensortype

1

0

thermocouple type L (-100...900°C), Fe-CuNi DIN

1

thermocouple type J (-100...1200°C), Fe-CuNi

2

thermocouple type K (-100...1350°C), NiCr-Ni

3

thermocouple type N (-100...1300°C), Nicrosil-Nisil

4

thermocouple type S (0...1760°C), PtRh-Pt10%

5

thermocouple type R (0...1760°C), PtRh-Pt13%

6

thermocouple type T (-200...400°C), Cu-CuNi

7

thermocouple type C (0...2315°C), W5%Re-W26%Re

8

thermocouple type D (0...2315°C), W3%Re-W25%Re

9

thermocouple type E (-100...1000°C), NiCr-CuNi

10

thermocouple type B (0/100...1820°C), PtRh-Pt6%

18

thermocouple Sonder (linearization necessary)

20

pt100 (-200.0 ... 100,0 °C)

21

pt100 (-200.0 ... 850,0 °C)

22

pt1000 (-200.0...8500.0 °C)

23

special 0...4500 Ohm (preset to KTY11-6)

24

special 0...450 Ohm (scaling necessary)

30

0...20mA / 4...20 mA (scaling necessary r page 36)

40

0...10V / 2...10 V

(scaling necessary r page36)

Configuration level

Digital 280-1

Configuration

24