beautypg.com

Configuration 27, Logi, Configuration level – West Control Solutions D280-1 User Manual

Page 27

background image

name

value range description

default

O.Src

signalsource for analog output OUT3 (only visible with O.TYP=1..5)

1

0

not active

1

controller output y1 (continuous)

3

process value

4

effective set-point Weff

5

control deviation xw (process value - set-point )

fOut

forcing OUT3 (only visible with BlueControl!)

0

0

no forcing

1

forcing via interface

LOGI

name

value range description

default

L_r

local / remote swith-over (remote: adjustment of all values via

front is blocked)

0

0

no function (switch-over via interface is possible)

1

always active

2

di1 switches

3

di2 switches(only visible with OPTION)

4

di3 switches(only visible with OPTION)

5

è -key switches

Err.r

reset of all stored messages of the errorlist

0

0

no function (switch-over via interface is possible)

2

di1 switches

3

di2 switches (only visible with OPTION)

4

di3 switches (only visible with OPTION)

5

è -key switches

tArA

0

0

no function (switch-over via interface is possible)

2

di1 switches

3

di2 switches (only visible with OPTION)

4

di3 switches (only visible with OPTION)

5

è -key switches

HoLd

0

0

no function (switch-over via interface is possible)

2

di1 switches

3

di2 switches (only visible with OPTION)

4

di3 switches (only visible with OPTION)

5

è -key switches

rES.L

0

0

no function (switch-over via interface is possible)

2

di1 switches

3

di2 switches (only visible with OPTION)

4

di3 switches (only visible with OPTION)

5

è -key switches

Configuration level

Digital 280-1

Configuration

27