6.2 Parameter
Func
name
value range
description
default
tEmP
1...99999 1
probetemperature for O
2
measuring
650
Pb1
1...99999 1
proportional band in phys. unit (z.B. °C)
100
ti1
1...99999
reset time 1 [s] (ti1=0 = off = switched off)
180
td1
1...99999
derivative time1 (heating) [s] (td1=0 = off = switched off)
180
t1
0,4...99999
min. cycle duration1 (heating) [s].
The smallest pulse duration is 1/4 x t1
10
SH
0...9999
neutral zone, e.g. switching difference signalunit [phys. unit]
2
Y2
-120...120
2nd control value [%] becomes effective with recognized process
value error -
FAIL
0
Y.Lo
-120...120
lower controller value limit [%]
0
Y.Hi
-120...120
upper controller value limit [%]
100
Y.0
-120...120
working point for controller value [%]
0
Sp.LO
-99999...99999
lower set-point limit [phys. unit]
0
SP.Hi
-99999...99999
upper set-point limit [phys. unit]
100
1 Valid for ConF/ othr/ DP = 0. At DP = 1/ 2/ 3/4 so 0,1 / 0,01 / 0,001, 0,0001.
InP
name
value range
description
default
InL
-19999...99999
input value of lower scaling point
0
OuL
-19999...99999
display value of lower scaling point
0
InH
-19999...99999
input value of upper scaling point
20
OuH
-19999...99999
display value of upper scaling point
20
t.F
0,1...999,9
filtertime constant [s]
0,5
b.F
0...99999
filterbandwidth
5
E.tc
0...100
external temperaturecompensation
OFF
Lim
name
value range
description
default
L.1
-19999...99999
lower limit value 1 (
L.1< -19999 = off)
-10
H.1
-19999...99999
upper limit value 1 (
H.1< -19999 = off)
10
HYS.1
0...99999
hysteresis of limit value 1
1
dEL.1
0...99999
alarm 1 delay
0
L.2
-19999...99999
lower limit value 2 (
L.2< -19999 = off)
OFF
H.2
-19999...99999
upper limit value 2
(
H.2< -19999 = off)
OFF
HYS.2
0...99999
hysteresis of limit value 2
1
dEL.2
0...99999
alarm 2 delay
0
L.3
-19999...99999
lower limit value 3 (
L.3< -19999 = off)
OFF
H.3
-19999...99999
upper limit value 3
(
H.3< -19999 = off)
OFF
HYS.3
0...99999
hysteresis of limit value 3
1
dEL.3
0...99999
alarm 3 delay
0
g
Resetting the controller configuration to factory setting (Default)
r chapter 11.1 (page 47)
Parameter setting level
Digital 280-1
Parameter