OUT3 AS UNIVERSAL OUTPUT
Galvanically isolated from the inputs.
Freely scalable
Resolution:
11 Bit
Timeconstant of DA-transducer T90
50 ms
Limitfrequency of the whole continuous
controller
> 2 Hz
Current output
0/4...20 mA configurable.
Signal range:
0...ca.21,5 mA
Max. load:
£ 500 W
Load effect:
0,02 % / 100
W
Resolution:
£ 22 mA (0,1%)
Accuracy
£ 40 mA (0,2%)
Voltage output (short-circuit proof)
0/2...10V configurable
Signal range:
0...ca.11 V
Min. load:
³ 2 kW
Load effect:
kein Einfluß
Resolution:
£ 11 mV (0,1%)
Accuracy
£ 20 mV (0,2%)
OUT3 used as transmitter supply
Output power:
22 mA /
³ 13 V
OUT3 used as logic output
Load
£ 500 W
0/
£ 20 mA
Load > 500
W
0/> 13 V
FUNCTIONS
Control behaviour
w
Signaller with adjustable siwtching
difference (ON/OFF controller)
w
PID controller (2-point and continuous)
Control parameters self-adjusting or manually adjustable via
front panel keys or BlueControl software.
Limit value functions
Monitoring is provided for: exceeded max., min. or max. and
min. limit value with adjustable hysteresis.
The following signals can be monitored:
w
Measured value
w
Process value
w
Control deviation
w
Control deviation with suppression after
start-up or set-point changes
w
Set-point
w
Correcting variable Y
Functions
w
Measured value monitoring
w
Measured value monitoring with storage.
Reset via front panel keys or digital input
w
Measured value change
w
Measured value change and storage
Several limit values and alarms can be combined by a logic OR
function and output e.g. as a common alarm.
ALARM + MAINTENANCE MANAGER
Displayof error messages, warnings and stored limit signallings
in the error list.
Messages are stored and can be reset manually.
Possible elements of the error list:
w
Sensor break, short circuit, polarity error
w
Self-tuning error
w
Stored limit values
-
E.g. recalibration warning
(when exceeding an adjustable number of
operating hours, a message is displayed)
-
E.g. maintenance interval of switching element
(when exceeding an adjustable number of
switching cycles, a message is displayed)
w
Internal errors (RAM, EEPROM, ...)
DISPLAY
Display
5-digit 19 mm LED
POWER SUPPLY
Dependent of order:
AC SUPPLY
Voltage:
90...250 V AC
Frequency:
48...62 Hz
Power consumption
approx. 7.3 VA
UNIVERSAL SUPPLY 24 V UC
AC voltage:
20,4...26,4 V AC
Frequency:
48...62 Hz
DC voltage:
18...31 V DC
Power consumption:
approx.. 7.3 VA
BEHAVIOUR WITH POWER FAILURE
Configuration, parameters and adjusted
set-points, control mode:
Non-volatile storage in EEPROM
BLUEPORT FRONT INTERFACE
Connection of PC via PC adapter (see "Accessory equipment").
The BlueControl software is used to configure, set parameters
and operate the KS4x-1.
BUS INTERFACE (OPTION)
Galvanically isolated
Physical:
RS 422/485