beautypg.com

4 manual tuning 20, 4 manual tuning, And x – West Control Solutions D280-1 User Manual

Page 20: Y= correcting variable y, Maximum process value v

background image

Start: heating power switched off
The controller waits 1,5 minutes (1).
Heating power Y is switched on (2).
At the reversal point, the self-tuning at-
tempt is finished and control to the
set-point is using the new parameters.

Start: at set-point
Heating power Y is switched off (1).
If the change of process value X was
constant during one minute and the con-
trol deviation is > 10% of

SP.Hi -

SP.LO (2), the power is switched on
(3). At the reversal point, the self-tu-
ning attempt is finished, and control to
set-point W is using the
new parameters.

4.4 Manual tuning

The optimization aid should be used with units on which the control parameters
shall be set without self-tuning.
For this, the response of process variable x after a step change of correcting va-
riable y can be used. Frequently, plotting the complete response curve (0 to
100%) is not possible, because the process must be kept within defined limits.
Values T

g

and x

max

(step change from 0 to 100 %) or

Dt and Dx (partial step re-

sponse) can be used to determine the maximum rate of increase v

max

.

Controller

Digital 280-1

Manual tuning

20

t

2

100%

Y

0%

X

W

start r

1

3

t turning point

blinks

lit

off

Tu

Tg

t

x

y

100%

0%

t

Yh

Xmax

{X

{t

y

= correcting variable

Y

h

=

control range

Tu

=

delay time (s)

Tg

=

recovery time (s)

X

max

=

maximum process value

V

max

=

Xmax

Tg

=

{

{

x

t

= max. rate of

increase of process value

t

100%

Y

0%

X

W

start r

1

2

t turning point

blinks

lit

off