West Control Solutions D280-1 User Manual
Page 25
name
value range description
default
41
special (-2,5...115 mV scaling necessary r page36)
42
special (-25...1150 mV scaling necessary r page 36)
43
special (-25...90 mV scaling necessary r page 36)
44
special (-500...500 mV scaling necessary r page 36)
45
special (-5...5 V scaling necessary r page 36)
50
potentiometer 0...160 Ohm
51
potentiometer 0...450 Ohm
52
potentiometer 0...1600 Ohm
S.Lin
linearization only adjustable with
S.tYP: 18, 23, 24, 30, 40 ... 45
0
0
none
1
Special linearization
Editing the linearization table with BlueControl (engineering tool) is
possible. The characteristic for KTY 11-6 temperature sensors is factory-set.
Corr
measurement value correction / scaling
0
0
no correction
1
offset-correction (in
CAL - level)
2
2-point-correction (in
CAL - level)
3
scaling (in
PArA - level)
fAI1
forcing INP (only visible with BlueControl!)
0
0
no forcing
1
forcing via interface
Lim
name
value range
description
default
Fnc.1
Fnc.2
Fnc.3
function of limit 1 (2, 3)
1
0
switched off
1
measured value monitoring
2
measured value monitoring + storing of alarm status.
A stored limit value can be set back via error list or digital input or
è -key (® LOGI/ Err.r).
3
signal change
4
signal change + storing of alarm status.
A stored limit value can be set back via error list or digital input or
è -key (® LOGI/ Err.r).
Src.1
Src.2
Src.3
source for limit value 1 (2, 3)
0
0
process value = absolut alarm
1
control deviation Xw (processvalue - set-point) = relative alarm
2
control deviation Xw (=relative alarm) with suppression at start
and with set-point change
3
measured value INP
6
set-point
7
y (controller output)
Hour
OFF..999999
operating hours (only visible with BlueControl!)
OFF
Swit
OFF..999999
operation cycle number (only visible with BlueControl!)
OFF
Configuration level
25
Configuration
Digital 280-1