name

value range description

default

41

special (-2,5...115 mV scaling necessary r page36)

42

special (-25...1150 mV scaling necessary r page 36)

43

special (-25...90 mV scaling necessary r page 36)

44

special (-500...500 mV scaling necessary r page 36)

45

special (-5...5 V scaling necessary r page 36)

50

potentiometer 0...160 Ohm

51

potentiometer 0...450 Ohm

52

potentiometer 0...1600 Ohm

S.Lin

linearization only adjustable with

S.tYP: 18, 23, 24, 30, 40 ... 45

0

0

none

1

Special linearization

Editing the linearization table with BlueControl (engineering tool) is

possible. The characteristic for KTY 11-6 temperature sensors is factory-set.

Corr

measurement value correction / scaling

0

0

no correction

1

offset-correction (in

CAL - level)

2

2-point-correction (in

CAL - level)

3

scaling (in

PArA - level)

fAI1

forcing INP (only visible with BlueControl!)

0

0

no forcing

1

forcing via interface

Lim

name

value range

description

default

Fnc.1
Fnc.2
Fnc.3

function of limit 1 (2, 3)

1

0

switched off

1

measured value monitoring

2

measured value monitoring + storing of alarm status.
A stored limit value can be set back via error list or digital input or

è -key (® LOGI/ Err.r).

3

signal change

4

signal change + storing of alarm status.
A stored limit value can be set back via error list or digital input or

è -key (® LOGI/ Err.r).

Src.1
Src.2
Src.3

source for limit value 1 (2, 3)

0

0

process value = absolut alarm

1

control deviation Xw (processvalue - set-point) = relative alarm

2

control deviation Xw (=relative alarm) with suppression at start

and with set-point change

3

measured value INP

6

set-point

7

y (controller output)

Hour

OFF..999999

operating hours (only visible with BlueControl!)

OFF

Swit

OFF..999999

operation cycle number (only visible with BlueControl!)

OFF

Configuration level

25

Configuration

Digital 280-1