4 o2 measurement 13, Operation – West Control Solutions D280-1 User Manual
Page 13
3.3.4 O
2
measurement
For measurement, lambda probes (
l probes) are used.
The electromotive force (in Volt) supplied by the
l probes is dependent of the
instantaneous oxygen content and of the temperature. Therefore, Digital 280-1
can display accurate measurement results only, provided that the probe tempera-
ture is known to the indicator.
Enter the temperature in °C in parameter
tEmP. When using heated l probes, the
probe temperature can be entered directly. When using non-heated
l probes, ho-
wever, the displayed values can be accurate only for a narrow temperature band.
g
Unless the probe temperature is known, we recommend using our KS90-1
Oxygen (temperature measurement via a second input).
Configuration:
Adjust O
2
measurement in function 1:
Func r Fnc.1
3
O2 measurement
Display: The displayed value is always a % value.
As it is mostly necessary to cover a wide measuring range, we recommend adju-
sting a high number of digits behind the decimal point during configuration, whe-
reby loss of high values is prevented due to floating decimal point display
(0,0001 (1 ppm) to 99999 is possible) .
Specify the number of digits behind the decimal point below othr :
othrr dP
0
0 digits behind the decimal point
1
1 digit behind the decimal point
2
2 digits behind the decimal point
3
3 digits behind the decimal point
4
4 digits behind the decimal point
Adjust the sensor type to one of the high-impedance voltage inputs in InP:
Specification in BlueControl
Effective measuring range
Inp.1r
S.tYP
41
Special ( 0...100 mV)
-2,5...115 mV
42
Special ( 0...1000 mV)
-25...1150 mV
43
Special ( -25...90 mV)
44
Special ( -500...500 mV)
These high-impedance inputs are not provided with break monitoring. If necessa-
ry, measurement input protection is possible via limit value processing.
Operation
Digital 280-1
Operating level
13